SV2 Series Safety Shut-off Valves
205
V2F, V2V
SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL
Fault
Category
Fault
Description
Detailed Description
Remediation Steps
Comments Fault
#
Security
Installer
password is not
configured.
Installer password is not
configured (set to default
value).
Configure Installer password to non-
default value.
96
OEM password
is not
configured.
OEM password is not
configured (set to default
value).
Configure OEM password to non-default
value.
97
Installer
account
temporarily
disabled
Installer account is
temporarily locked down due
to too many login attempts
with wrong password.
Wait at least 1 minute before new attempt
to login.
If message is present with no attempts to
login, another device on network might
be trying to login. Find this device and
disable it before trying to login.
98
OEM account
temporarily
disabled
OEM account is temporarily
locked down due to too many
login attempts with wrong
password.
Wait at least 1 minute before new attempt
to login.
If message is present with no attempts to
login, another device on network might
be trying to login. Find this device and
disable it before trying to login.
99
Installer
password
reset feature
temporarily
disabled
Installer password reset
feature is temporarily
disabled due to too many
unsuccessful reset attempts.
Wait at least 1 minute before new attempt
to reset password.
If message is present with no attempts to
reset password, another device on network
might be trying to reset password. Find
this device and disable it before trying to
reset password.
100
OEM password
reset feature
temporarily
disabled
OEM password reset feature
is temporarily disabled due
to too many unsuccessful
reset attempts.
Wait at least 1 minute before new attempt
to reset password.
If message is present with no attempts to
reset password, another device on network
might be trying to reset password. Find
this device and disable it before trying to
reset password.
101
OEM reset
password is not
set.
OEM reset password is not
configured although the
feature is enabled.
Configure OEM reset password OR disable
the OEM password reset feature.
102
Solenoid 1 Solenoid 1 relay
fault
Solenoid 1 relay was
detected closed during SSOV
cycle test
1.) Reset valve and burner management
system, observing valve / burner
operation.
2.) If fault persists, replace valve main
electronics.
0