SV2 Series Safety Shut-off Valves
200
32-00029—02
Fault
Category
Fault
Description
Detailed Description
Remediation Steps
Comments Fault
#
POC
POC (proof of
closure) of MV1
not verified
Proof of closure verification
procedure not completed.
1.) Ensure the Proof of Closure setup/
acceptance procedure has been
performed. Go to the Setup & Tests screen,
select the Settings menu and the Proof
of Closure tab. Follow the prompts and 'i'
page information.
2.) Perform the Safety Parameters
Verification procedure. Go to Setup & Tests
screen, press the button labeled Verify
Safety Parameters and follow the prompts.
If this procedure is not completed while
logged in, the valve will lockout when the
login times out and the valve will not be
operational.
NOTE: The Proof of Closure setup/
acceptance and Safety Parameters
Verification procedures validate the
POC(s) exist and are properly wired to
the valve electronics assembly. They also
validate proper procedure was followed
if the valve electronics orientation was
swapped or the valve electronics assembly
was replaced in the field.
77
POC (proof of
closure) of MV2
not verified
Proof of closure verification
procedure not completed.
1.) Ensure the Proof of Closure setup/
acceptance procedure has been
performed. Go to the Setup & Tests screen,
select the Settings menu and the Proof
of Closure tab. Follow the prompts and 'i'
page information.
2.) Perform the Safety Parameters
Verification procedure. Go to Setup & Tests
screen, press the button labeled Verify
Safety Parameters and follow the prompts.
If this procedure is not completed while
logged in, the valve will lockout when the
login times out and the valve will not be
operational.
NOTE: The Proof of Closure setup/
acceptance and Safety Parameters
Verification procedures validate the
POC(s) exist and are properly wired to
the valve electronics assembly. They also
validate proper procedure was followed
if the valve electronics orientation was
swapped or the valve electronics assembly
was replaced in the field.
78