SV2 Series Safety Shut-off Valves
191
V2F, V2V
SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL
Fault
Category
Fault
Description
Detailed Description
Remediation Steps
Comments Fault
#
Fuel/Air
FARMOD
Factory
Calibration data
invalid
Fuel/Air Ratio Module does
not contain valid factory
calibration data.
1.) Replace Fuel/Air Ratio Module.
2.) Accept new Fuel/Air Ratio Module on
the FARMOD tab in the Setup & Tests
menu of user interface.
3.) Recommission partially or fully as
desired.
4.) Reset valve and burner management
system, monitoring for proper operation.
86
Control Valve
Full Stroke
Undefined
The full stroke of the control
valve is not defined.
Replace the valve and re-commission.
88
Control Valve
Full Stroke
Mismatch
The recorded full stroke of
the control valve does not
match valve size.
Replace the valve and re-commission.
89
Fuel/Air Base
Curve Min not
defined
Fuel/Air Ratio base curve
minimum value has not been
defined. In installer mode
this fault is ignored.
Commission or load the base fuel/air
curve, ensuring the minimum firing rate is
entered.
91
Fuel/Air Base
Curve Max not
defined
Fuel/Air Ratio base curve
maximum value has not been
defined. In installer mode
this fault is ignored.
Commission or load the base fuel/air
curve, ensuring the maximum firing rate is
entered.
92
Fuel/Air Base
Curve not
commissioned
Fuel/Air Ratio base curve
initial amplification setting/
value has not been defined.
Enter a value for the initial
amplification of the base
curve and reset the valve
in in OEM commissioning
mode.
Commission or load the base fuel/air
curve.
93