SV2 Series Safety Shut-off Valves
22
32-00029—02
Open
Closed
Self Test
Fault
LGP
HGP
Open
Closed
Reset
M35729
Fig. 14: Valve interface.
Table 4. Valve Interface LED Descriptions.
LED
Purpose
Applicable
Models
Open
If a POC (proof of closure switch) is present on the valve, this LED indicates that the valve seat is
open. This gives visual position indication per FM (Factory Mutual) 7400 and ANSI Z21.21 / CSA
6.5. LED gives status indication of the valve seat over which the LED is situated.
1
If a POC (proof of closure switch) is NOT present, this LED indicates the solenoid is powered.
All valve
models
Closed
If a POC (proof of closure switch) is present on the valve, this LED indicates that the valve seat is
closed. This gives visual position indication per FM (Factory Mutual) 7400 and ANSI Z21.21 / CSA
6.5. LED gives status indication of the valve seat over which the LED is situated.
1
If a POC (proof of closure switch) is NOT present, this LED indicates the solenoid is not powered.
Self Test
The Self Test LED indicates a valve test is being performed. Self Tests include circuit check
during initial power-up, external and internal VPS, leak detection test, manual low gas or high gas
pressure tests.
NOTE: On BASIC (5) intelligence valves, this only indicates a circuit check.
Fault
Indicates a fault condition exists.
Refer to the
VALVE FAULT CODES
section of this manual for detailed fault descriptions.
LGP
Indicates a Low Gas Pressure fault condition exists when a SV2 Series Pressure Module is used on
the valve and programmed.
NOTE: The Fault LED will also be lit while this fault is active.
All models
with
Intelligent
Features
of 6
HGP
Indicates a High Gas Pressure fault condition exists when a SV2 Series Pressure Module is used on
the valve and programmed.
NOTE: The Fault LED will also be lit while this fault is active.
1.
Valve electronics orientation is ordered as left-hand or right-hand mounted from the factory (defined as being viewed from the valve gas outlet / burner end).
If the electronics orientation is changed in the field (as illustrated in CHAPTER 10:
CHANGING VALVE / ELECTRONIC ORIENTATION
in this manual), the LED
orientation procedure must be completed to ensure the LED annunciation continues to indicate status of the valve seat over which it is situated. This procedure
is part of the instructions in Chapter 10.