SV2 Series Safety Shut-off Valves
208
32-00029—02
Fault
Category
Fault
Description
Detailed Description
Remediation Steps
Comments Fault
#
VPS
VPS Test Failure Valve 2 proving sequence
has failed.
1.) Check the piping train (is MOV closed,
piping flanges tight, O-ring leakage), main
electronics wiring and Pressure Module
connection to it. For wiring, refer to the
installation instructions, 32-00018. Reset
valve and repeat the VPS test.
2.) If fault persists, check system gas
pressure and repeat the VPS test.
3.) If fault persists, replace Pressure
Module.
4.) Accept new Pressure Module on the
PRESSMOD tab in the Setup & Tests
menu.
5.) Recommission the Hi-Gas and Lo-Gas
pressure limits. Repeat leak detection test.
6.) If fault persists, replace valve.
Warning
indication
for SV2
valve.
But this
condition
will likely
cause a
burner
controller
lockout.
63
TIGHTENING TORQUES
A summary of all tightening torques for the SV2 Series valves and components can be found in
Table 2927
.
Table 27. SV2 Series maximum tightening torques.
Category
Item
Picture
Maximum Tightening
Torque
Nm
In-lbf
Valve
enclosure
Front electronics cover
(NEMA 1/IP20 and NEMA 4/
IP66
M37170
Open
Closed
Self Test
Fault
LGP
HGP
Open
Closed
Reset
Open
Closed
Self Test
Fault
LGP
HGP
Open
Closed
Reset
1.26-1.54
11-13.63
Rear solenoids cover
(NEMA 1/IP20 and NEMA 4/
IP66
M37171
2.2-2.35
19.5-20.8
Electrical enclosure fastener
tabs to valve metal bonnet
(NEMA 1/IP20 and NEMA 4/
IP66
M37172
4-5
35-44
Replacement electronics
assembly to the electronics
base
Open
Closed
Self Test
Fault
LGP
HGP
Open
Closed
Reset
SOLENOID 1
SOLENOID 2
L1 N
MAINS
SUPPLY
MAINS CHASSIS
GROUND
ILK ILK VPS POC MV2 MV1
OUT IN
RS-485
MODBUS
+
–
C
OFF
BIAS
TERMIN.
BIAS
ON
1
2
3
MODBUS
GND IN1 GND IN2
A
N
A
L
O
G
FIRE
RATE
O2
SENSOR
MOTOR
PRESSURE
FUEL/AIR
MCR37173
SOLENOID 1
PROOF OF CLOSURE
POC 1
POC 2
SOLENOID 2
MAINS
SUPPLY
L1 N
MAINS CHASSIS
GROUND
ILK ILK VPS POC MV2 MV1
OUT IN SW
CONTROL WIRING
RS-485
MODBUS
+
–
C
OFF
BIAS
TERMIN.
BIAS
ON
1
2
3
MODBUS
GND IN1 GND IN2
A
N
A
L
O
G
FIRE RATE O2 SENSOR
MOTOR
PRESSURE
FUEL/AIR
Open
Closed
Self Test
Fault
LGP
HGP
Open
Closed
Reset
1.69-1.8
15-16