SV2 Series Safety Shut-off Valves
26
32-00029—02
M35630
O-RING
PIPE ADAPTER
MOUNTING
SCREWS
PIPE
ADAPTER
OUTLET
PRESSURE
TAP
FUEL AIR
MODULE
VENT PIPE
GAS VALVE
DIRECTION
ARROW
GUIDE
LOCATING
HOLES FOR
PRESSURE
MODULE
PRESSURE
MODULE
PRESSURE
MODULE
MOUNTING
SCREWS
Fig. 17: Valve exploded view.
The diagram below shows all of the possible pressure access/tap locations on each side of the valve. These locations may be
used for the functions listed in
Table 5
or general pressure measurement. Each pressure access/tap location on the valve body
is either 1/8 in (3mm) NPT or BSP, depending on what is ordered from the factory. Typically, for 24VAC or 100-120VAC, taps are
NPT and for 200-240VAC, taps are BSP. Refer to
Fig. 1
Valve nomenclature for further information. Digit # 6 in the valve model
identifies the port thread type.
The flange pressure taps are 1/8-27 in (3mm) if an NPT flange is ordered or 1/8-28 in (3mm) if a BSP flange is ordered from the
factory.
NOTES: When replacing pressure access port plugs in the field, the tightening torque should be 6-8 Nm (53-71 in-lbf).