Page 76
STT700 Series HART/DE Option User’s Manual
Revision 1
6.10 Manually Setting the Process Variable Range
This procedure applies to DE transmitters operating in both DE mode and analog (current) mode.
During this procedure, the PV input will be set to 0%, which will be applied as the LRV. Further, the
PV input will be set to 100% and applied as the URV.
1.
Establish the test connections shown below. Then start the MC Toolkit application to display
the DE MAIN MENU.
Figure 14
– Setup to Manually Set the PV LRV and URV