Page 42
STT700 Series HART/DE Option User’s Manual
Revision 1
Online/Device Setup/Basic
Configuration/
4-20mA Outputs
PV Damp
Enter a value for damping of the device
output. Entries may be any value from 0.00
to 102.00 seconds.
Poll Address
Loop Current Mode
The following output-related values and
operations are available in this menu:
Poll Address: Select HART short address 0
to 63.
Loop current mode: Select the Loop
Current Mode configuration:
“Enable”: enables loop current mode
(analog output will operate as a 4 to 20 mA
signal consistent with the transmitter
output)
“Disable”: disables loop current mode
(analog output will be fixed at 4 mA)
NAMUR Option
Select from the following:
Namur Selection: select to enable or
disable the Namur option for the output.
(Refer to the PV Ranges/Limits chart) for
effect on output signal.
Namur Level: Displays a diagram of the
operating range and failsafe range of the
Analog output for Normal and Namur
configurations.
PV % range
Displays the current value of transmitter
Output in %
PV LTL
Lower Transducer Limits
PV UTL
Upper Transducer Limits
Summary
Displays the current values under Basic Configuration Menu for all of
the pertinent operating parameters listed in this table. Parameters are
not configurable in this menu