Revision 1
STT700 Series HART/DE Option User’s Manual
Page 41
Device Setup/Basic
Configuration/Process
Values/PV [Loop]
PV[Loop]
Displays the current value of the Primary
Variable (loop PV according to the control
mode selected) in user selected engineering
units
Device Setup /Basic
Configuration/Process
Values/SV [Cold Jn.
Temperature]
SV [Cold Jn.
Temperature]
Displays the current value of the Secondary
Variable (CJ temperature) in user selected
engineering units
Device Setup /Basic
Configuration/Process
Values/TV[Sensor 1]
TV [Sensor 1]
Displays the sensor input 1 value
Device Setup /Basic
Configuration/Process
Values/QV[Sensor 2]
QV [Sensor 2]
Displays the sensor input 2 value
Online/Device Setup/Basic
Configuration/
Process Values
PV Unit
Select one of the pre-programmed
engineering units. STT700 temperature
readings can be displayed in the following
engineering units:
o
C,
o
F,
o
Kelvin,
o
R, mV, Ohms
PV Damp
Enter a value for damping of the device
output. Entries may be any value from 0.00
to 102.00 seconds.
SV Unit
Select the desired unit for measurement of
the Secondary Variable (cold junction
temperature) Selections available are:
o
C,
o
F,
o
R, Kelvin.
Online Menu Flow
Parameter menu/
name
Description/Valid values
Basic Configuration / 4-20mA Outputs
Device Setup /Basic
Configuration/4-20mA
Outputs/PV Loop current
PV Loop current
Displays the current value of Analog Output
in mA
PV % rnge
Displays the current value of transmitter
output in %
PV LRV
Displays the current value of the Lower
Range Value (input which represents 0%
output) in user selected engineering units.
This value may be configured to any value
within the range.
PV URV
Displays the current value of the Upper
Range Value (input which represents 100%
output) in user selected engineering units.
This value may be configured to any value
within the range.