STT700 Series HART/DE Option User’s Manual
Revision 1
Online/Device
Setup/Advanced
Configuration/Services
Loop Test
This function enables the user to test the
Analog Output measurement at any value
over the full operational range. Select a
current value to apply to the output and verify
the measured current on the loop with a
calibrated meter.
Note that this function is only available when
“Loop mA” (Loop Current mode) is Enabled.
Lock/Unlock Device
Select the Lock state for access by HART
configuration tools.
If “Yes” is selected to lock the device, also
select “Yes” or “No” to choose whether or not
the lock is “permanent.” If the lock is not
permanent, it will be cleared on power cycle or
Master Reset of the device.
If “Yes” is selected to unlock the device, the
lock state will be cleared.
Summary
Displays the current values under Advanced Configuration Menu for all
of the pertinent operating parameters listed in this table. Parameters
are not configurable in this menu