Revision 1
STT700 Series HART/DE Option User’s Manual
Page 47
Online/Device
Setup/Advanced
Configuration/Calibration
Clear all user calibration adjustments.
S2 Cal Hi Records:
Displays the time and date history records for the
last three URV Correct calibrations.
S2 Cal Lo Records:
Displays the time and date history records for the
last three LRV Correct calibrations.
S2 Reset Correct Records:
Displays the time and date history records for the
last three times Reset Corrects was issued.
Online Menu Flow
Parameter menu/
name
Description/Valid values
Advanced Configuration/CVD (Callendar-Van Dusen constants)
Online/Device
Setup/Advanced
Configuration/CVD
CVD 1 Activate
CVD 1 ON: CVD feature enabled for Sensor 1
CVD 1 OFF: CVD feature disabled for Sensor 1
Online/Device
Setup/Advanced
Configuration/CVD
CVD 2 Activate
CVD 2 ON: CVD feature enabled for Sensor 2
CVD 2 OFF: CVD feature disabled for Sensor 2
Advanced Configuration/CVD1 (Callendar-Van Dusen constants for sensor 1)
Online/Device
Setup/Advanced
Configuration/CVD 1
Coefficients
Write CVD 1
Coefficients
User can configure CVD coefficients
R0, Alpha, Delta and Beta
CVD 1 Low Limit
CVD 1 resistance for corresponding the low
temperature calibration point
CVD 1 High Limit
CVD 1 resistance for corresponding the high
temperature calibration point
R0
Resistance at 0
°
C
Alpha
Alpha CVD coefficient for sensor 1
Delta
Delta CVD coefficient for sensor 1
Beta
Beta CVD coefficient for sensor 1