Sensepoint XCD RTD Technical Manual SPXCDHMRTEN Issue 1
13
5.3.2 Remote Sensor Mounting
A remotely mounted sensor should be mounted using a suitable junction box or approved
electrical conduit scheme. For further details regarding mounting sensors to suitable
junction boxes refer to the relevant sensor manual.
To remotely mount the sensor, follow the procedure below.
1. Select a suitably certified junction box.
2. Fit the sensor to the junction box (refer to sensor manual)
3. Connect the junction box to the transmitter using suitable cable and cable glands
Note: The maximum cable length between the remotely mounted sensor and the
XCD RTD transmitter is 30 meters(100 feet).
4. Terminate the wires from the sensor in the transmitter as shown in section 6.
Diagram 7: Remote Sensor Mounting
NTS
SA
17-Jul-09
Sensepoint XCD
RTD Transmitter
Installation Drawing
3001G0496
A
17/JUL/09
New
Drawing
J.Y.JIN
08/OCT/09
B
Add
Sheet4
J.Y.JIN
C
27/OCT/09
Change
Title
J.Y.JIN
J.Y.JIN
29/OCT/09
D
Remove
Adaptor
E
02/NOV/09
Modify
Text
J.Y.JIN
3001G0496
Summary of Contents for Sensepoint XCD RTD
Page 1: ...Technical Manual Sensepoint XCD RTD Remote Toxic Detector Technical Manual ...
Page 56: ...Sensepoint XCD RTD Technical Manual SPXCDHMRTEN Issue 1 56 17 5 Mounting Bracket Drawing ...
Page 58: ...Sensepoint XCD RTD Technical Manual SPXCDHMRTEN Issue 1 58 China GB Ex English Version ...
Page 59: ...Sensepoint XCD RTD Technical Manual SPXCDHMRTEN Issue 1 59 China PA Certification ...
Page 60: ...Sensepoint XCD RTD Technical Manual SPXCDHMRTEN Issue 1 60 18 2 Korea KTL ...
Page 63: ...Sensepoint XCD RTD Technical Manual SPXCDHMRTEN Issue 1 63 ATEX for Sensor ...
Page 65: ...Sensepoint XCD RTD Technical Manual SPXCDHMRTEN Issue 1 65 IEC Ex for Sensor ...
Page 66: ...Sensepoint XCD RTD Technical Manual SPXCDHMRTEN Issue 1 66 18 5 ATEX Name Plate ...