Sensepoint XCD RTD Technical Manual SPXCDHMRTEN Issue 1
48
14 General specification
Sensepoint XCD Transmitter
Use
3-wire, 4-20mA, gas detector transmitter for use with toxic gas sensors. For the protection
of personnel and plant from toxic gas hazards.
Electrical
Input Voltage Range:
Max Power Consumption:
Current output
≥0.0<1.0 mA
4.0 mA to 20.0 mA
2.0 mA or 4.0 mA (17.4 mA)
22.0 mA
Terminals
Relays
Communication
18 to 32Vdc (24Vdc nominal)
Max 5 Watts. at 24Vdc (see section 2 regarding maximum in
rush current)
4-20mA
Fault (refer to table 5 section 12.3 for further details).
Normal gas measurement
Inhibit (during configuration/user settings)
Maximum over range
18 x screw terminals suitable for wire diameter 0.5mm
2
to
2.5mm
2
(20AWG to 13AWG).
3 x 5A@250VAC. Selectable normally open or normally closed
(switch) and energized/de-energized (programmable).
RS485, Modbus RTU (Pending)
Construction
Material
Epoxy painted aluminium alloy or 316 Stainless Steel
Weight
Aluminium alloy: 2.0kg, 316 Stainless Steel: 4.5kg
Mounting
Pole or wall mounting
Entries
2 x M20
Detectable Gases & Performance (See notes below)
Certification
China
Korea
European
International
GB Ex d IIC T4 GB3836.1&2 -2000, PA, (CCCF – Pending)
KTL Ex d IIC T6 (-40ºC to +65ºC)
ATEX Ex II 2 GD Ex d IIC Gb T6(Ta -40ºC to +65ºC) Ex tb IIIC T85ºC Db IP66
IEC Ex d IIC Gb T6(Ta -40ºC to +65ºC) Ex tb IIIC T85ºC
Db IP66
CE
EN50270:2006 EN6100-6-4:2007
Environmental
IP Rating
IP66 in accordance with EN60529:1992
Operating
Temperature
-40ºC to +65ºC/ -40ºF to +149ºF
Note: The detector display may become illegible at temperatures below -40°C, but the detector continues its gas monitoring
function. The display is not damaged and recovers when the temperature rises back above -20 °C.
Sensor operating temperature range is dependent on gas type. Please refer to the Sensepoint Technical Handbook for details.
Operating
Humidity
Continuous 20-90%RH (non condensing), Intermittent 10-99%RH (non condensing)
Operating
Pressure
90-110kPa
Storage
Conditions
-25°C to +65°C (-13°F to +149°F)
NOTES
Please refer Sensepoint Technical Handbook for detail.
Gas Name
Displayed
Name
Range
Lower
Alarm
Lower
Alarm
Type
Higher
Alar m
Higher
Alarm
Type
Lowest
alarm
level
20.0 ppm
4.0ppm
Rising
8.0ppm
Rising
2.0ppm
50.0 ppm
10.0ppm
Rising
20.0ppm
Rising
5.0ppm
Hydrogen Sulfide
H
2
S
100 ppm
20ppm
Rising
40ppm
Rising
10ppm
100 ppm
30ppm
Rising
60ppm
Rising
10ppm
200 ppm
40ppm
Rising
80ppm
Rising
20ppm
Carbon M onoxide
CO
500 ppm
100ppm
Rising
200ppm
Rising
50ppm
5.0 ppm
0.5 ppm
Rising
2.0ppm
Rising
0.5ppm
Chlorine
Cl
2
15.0 ppm
1.5 ppm
Rising
6.0ppm
Rising
1.5ppm
50.0 ppm
20.0ppm
Rising
30.0ppm
Rising
5.0ppm
100 ppm
20ppm
Rising
40ppm
Rising
10ppm
Am m onia
NH
3
1000 ppm
200ppm
Rising
400ppm
Rising
100ppm
H
2
1000ppm
200ppm
Rising
400ppm
Rising
100ppm
Hydrogen
H
2
9999 ppm
2000ppm
Rising
4000ppm
Rising
1000ppm
Nitrogen M onoxide
NO
100 ppm
20ppm
Rising
40ppm
Rising
10ppm
SO
2
15.0 ppm
2.0ppm
Rising
6.0ppm
Rising
1.5ppm
Sulphur Dio xide
SO
2
50.0 ppm
5.0ppm
Rising
20.0ppm
Rising
5.0ppm
Nitrogen Dioxide
NO
2
10.0 ppm
2.0ppm
Rising
4.0ppm
Rising
1.0ppm
Oxygen
O
2
25.0 % V/V
19.5% Vol
Falling
23.5% Vol
Rising
10.0% Vol
Summary of Contents for Sensepoint XCD RTD
Page 1: ...Technical Manual Sensepoint XCD RTD Remote Toxic Detector Technical Manual ...
Page 56: ...Sensepoint XCD RTD Technical Manual SPXCDHMRTEN Issue 1 56 17 5 Mounting Bracket Drawing ...
Page 58: ...Sensepoint XCD RTD Technical Manual SPXCDHMRTEN Issue 1 58 China GB Ex English Version ...
Page 59: ...Sensepoint XCD RTD Technical Manual SPXCDHMRTEN Issue 1 59 China PA Certification ...
Page 60: ...Sensepoint XCD RTD Technical Manual SPXCDHMRTEN Issue 1 60 18 2 Korea KTL ...
Page 63: ...Sensepoint XCD RTD Technical Manual SPXCDHMRTEN Issue 1 63 ATEX for Sensor ...
Page 65: ...Sensepoint XCD RTD Technical Manual SPXCDHMRTEN Issue 1 65 IEC Ex for Sensor ...
Page 66: ...Sensepoint XCD RTD Technical Manual SPXCDHMRTEN Issue 1 66 18 5 ATEX Name Plate ...