19.2 Meter Multiplication Factors for Sensepoint XCD-IR Propane
It is possible to apply a linear cross reference factor to the output of a sensor characterized
for propane and achieve the results shown in the graph below.
Reasonable accuracy is maintained to at least the 50% LEL equivalent values of the
cross-referred gasses.
XCD IR Propane Sensor (Full scale 2% Vol/100%LEL)
Diagram 18. Sensepoint XCD-IR (Propane) Sensor with linear cross-reference factor
appliedfactor applied
Use the following multiplying factors to cross-refer to the propane reading:
Gas
Multiplication Factor
Ethylene
3.43
nButane
0.97
nPentane
0.89
Table 17. Multiplying Factors
NOTE
Honeywell Analytics recommends that users verify the accuracy of their instruments using
test gasses wherever possible. Cross-referred measurements should be used as a guide
only, not as absolute values.
Caution: These factors only apply to gas concentrations expressed in % Volume terms.
When using a linear cross reference factor the temperature compensation is
based upon propane, and there may be errors at temperatures away from the calibration
temperature.
Summary of Contents for Sensepoint XCD RFD
Page 1: ...Technical Handbook Sensepoint XCD RFD Remote Flammable Detector ...
Page 65: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 65 China PA Certification ...
Page 66: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 66 18 2 Korea KTL ...
Page 68: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 68 ATEX for Sensor ...
Page 70: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 70 IEC Ex for Sensor ...
Page 79: ...www norrscope com ...