19.Promptly switch off the calibration span gas and remove the Sensepoint XCD
Gassing Cap from the sensor to allow the gas to disperse.
20.When the reading falls below 50% of the calibration gas level the display indicates a
countdown .
21. When the countdown is finished, the calibration procedure is complete.
22. The instrument returns to the ‘Set CAL’ menu. Activate the ‘
’ or ‘
’ switch to
select another menu or select ‘QuIT’ to return to normal monitoring mode.
Note: Remember to always replace the Weather Protection and other accessories.
Summary of Contents for Sensepoint XCD RFD