6.1 Transmitter Wiring
The Sensepoint XCD RFD transmitter may be wired in either Current SOURCE or Current
SINK configuration. These two options are offered to allow greater flexibility in the type of
control system that it can be used with. SOURCE/SINK is selectable via the switch located
on the back side of the display module; accessible by removing the display module during
installation / commissioning (see section 9).
Caution: All electrical connections should be made in accordance with any relevant
local or national legislation, standards or codes of practice.
Caution: 250ohm load resistor (RL) is installed in the factory, In case of connection
with controller, this resistor should be removed because controller has load resistor
internally.
Note: Terminate cable screen at detector or controller, not both.
XCD Source 3 Wire 4-20mA (Source)
XCD Sink 3 Wire 4-20mA (Sink)
Controller
+VE
Signal
1
2
3
Detector
+VE
Signal
-VE
R
L
-VE
1
3
2
Controller
+VE
Signal
1
2
3
Detector
+VE
Signal
-VE
R
L
-VE
1
3
2
R
L
Controller
+VE
Signal
1
2
3
Detector
+VE
Signal
-VE
-VE
1
3
2
R
L
Controller
+VE
Signal
1
2
3
Detector
+VE
Signal
-VE
-VE
1
3
2
Summary of Contents for Sensepoint XCD RFD
Page 1: ...Technical Handbook Sensepoint XCD RFD Remote Flammable Detector ...
Page 65: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 65 China PA Certification ...
Page 66: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 66 18 2 Korea KTL ...
Page 68: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 68 ATEX for Sensor ...
Page 70: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 70 IEC Ex for Sensor ...
Page 79: ...www norrscope com ...