5.1 Mounting and location
Gas detectors should be mounted where a potential hazard of gas is most likely to be
present. The following points should be noted when locating gas sensors.
• When locating detectors consider the possible damage caused by natural events e.g.
rain or flooding.
• Consider ease of access to the gas detector for functional testing and servicing.
• Consider how escaping gas may behave due to natural or forced air currents.
Note: The placement of gas detectors should be determined following the advice of
experts having specialist knowledge of gas dispersion, experts having knowledge of
the process plant system and equipment involved, safety and engineering personnel.
The agreement reached on the location of detectors should be recorded.
5.2 Mounting the transmitter
The Sensepoint XCD RFD transmitter has an integral mounting plate consisting of four
mounting holes on the transmitter body. The transmitter may be fixed directly to a surface
mounting, or to a horizontal or vertical pipe/structure, 40.0-80.0mm (1.6 to 3.1 inches) in
diameter/cross section. The Pipe Mounting Bracket accessory (optional accessory) may
be used for this purpose.
Caution: The location of gas detectors should be made in accordance with any relevant
local and national legislation, standards or codes of practice. Always replace sensors
with a sensor of the same type.
Diagram 5: Outline and mounting dimensions
All dimensions are
shown in mm.
M20 or 3/4 NPT entries
Summary of Contents for Sensepoint XCD RFD
Page 1: ...Technical Handbook Sensepoint XCD RFD Remote Flammable Detector ...
Page 65: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 65 China PA Certification ...
Page 66: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 66 18 2 Korea KTL ...
Page 68: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 68 ATEX for Sensor ...
Page 70: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 70 IEC Ex for Sensor ...
Page 79: ...www norrscope com ...