Sensepoint XCD RFD Technical Manual
SPXCDHMRFEN Issue 4_08-2016
42
13.2.1 Configuration mode operation table
Configuration mode allows the user to perform calibration and configure parameters
such as full scale range, calibration gas level, calibration interval, inhibit current &
timeout, alarm settings, relay settings, set a password, etc. To activate Configuration
mode hold the magnet over the ENTER switch for at least 3 seconds and then remove.
Configuration mode can be password protected to prevent unauthorized personnel from
changing parameters. Initially the password is set to ‘0000’ meaning it is disabled. While in
Configuration mode, the output current of the detector is inhibited to prevent false alarms.
Use the table below to help navigate the menus and make configuration changes. The
menus are shown in the left hand column. Use
to select the required menu and ‘
’
to enter. Follow the information and instructions in the table from left to right from the
required menu.
OK
OK
OK
OK
SEt
CAL
1
GAS NAME, ZERO
CONCENTRATION AND
FLASHING ‘ ’ ICON
DISPLAYED. APPLY ZERO
GAS AND USE ‘
’ WHEN
READING IS STABLE. ‘ZEro
PASS’ DISPLAYED IF OK,
‘ZEro FAIL’ IF NOT.
‘SPAN’ DISPLAYED AND
‘YES’ FLASHING TO
ASK IF YOU NOW WANT
TO PERFORM SPAN
CALIBRATION. USE ‘
’
TO PROCEED OR USE
TO SELECT ‘No’
AND RETURN TO MENU
MODE.
‘GAS’ TARGET
CONCENTRATION
FLASHING AND ‘ ’
ICON DISPLAYED.
USE
TO
CHANGE GAS
CONCENTRATION
AND ‘
’ TO START
SPAN CALIBRATION.
GAS NAME, CURRENT
CONCENTRATION AND
FLASHING ‘ ’ ICON
DISPLAYED. APPLY
SPAN GAS AND USE ‘
’
WHEN READING STABLE.
IF OK ‘PASS’ & ‘PurG’
DISPLAYED (IF FAIL
‘SPAN FAIL’ DISPLAYED
AND RETURNS TO
MENU). REMOVE SPAN
GAS. WHEN READING
<50% OF SPAN POINT,
COUNTDOWN BEGINS &
UNIT RETURNS TO MENU
MODE.
SEt
rAn9
BAR GRAPH INDICATING
CURRENT RANGE, ‘rAn9’
DISPLAYED & CURRENT
RANGE FLASHES. USE
TO SELECT DIFFERENT
RANGE
IF RANGE IS CHANGED,
‘CAL’ DISPLAYED AND
‘YES’ FLASHING TO
ASK IF YOU NOW
WANT TO PERFORM
CALIBRATION. USE ‘
’
TO PROCEED OR USE
TO SELECT ‘No’.
IF RANGE IS
CHANGED, ‘ALrm’
DISPLAYED AND
‘YES’ FLASHING TO
ASK IF YOU NOW
WANT TO MODIFY
ALARM SETTINGS.
USE ‘
’ TO PROCEED
OR USE
TO
SELECT ‘No’ AND
RETURN TO MENU
MODE.
UNIT RETURNS TO MENU
MODE
ConF
Inhb
‘Inhb’ DISPLAYED WITH
‘ ’ ICON FLASHING.
CURRENT INHIBIT mA
VALUE FLASHES. USE
TO SELECT NEW VALUE
‘tImE’ DISPLAYED WITH
‘ ’ ICON. FLASHING
CURRENT INHIBIT
TIMEOUT PERIOD
(MINUTES) FLASHES.
USE
TO SET
NEW TIMEOUT. (IF
SET TO 0 OUTPUT
IS PERMANENTLY
INHIBITED)
UNIT RETURNS TO
MENU MODE
SEt
PASS
‘PASS’ DISPLAYED WITH
FIRST DIGIT PLACE ICON
OF THE PASSCODE
FLASHING. USE
TO
SELECT 1
ST
DIGIT OF
CURRENT PASSWORD.
USE
TO MOVE TO NEXT
DIGIT AND SET REST OF
PASSCODE.
UNIT RETURNS TO
MENU MODE
CAL
Int3
2
‘Int’ DISPLAYED WITH
CURRENT CALIBRATION
INTERVAL FLASHING.
USE
TO CHANGE
INTERVAL.
‘duE’ DISPLAYED AND
‘No’, ‘LCd’ OR ‘ALL’
FLASHING. USE
TO SELECT REQUIRED
CAL DUE WARNING
OUTPUT.
UNIT RETURNS TO
MENU MODE
Summary of Contents for Sensepoint XCD RFD
Page 1: ...Technical Handbook Sensepoint XCD RFD Remote Flammable Detector ...
Page 65: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 65 China PA Certification ...
Page 66: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 66 18 2 Korea KTL ...
Page 68: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 68 ATEX for Sensor ...
Page 70: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 70 IEC Ex for Sensor ...
Page 79: ...www norrscope com ...