Sensepoint XCD RFD Technical Manual
SPXCDHMRFEN Issue 4_08-2016
78
A.2 Modbus Registers
ModBus
Register
Address
Information
R/W
Type
Size
Note
30001
Main SW Version of XCD
R
u8
1
30002
EEP Version of XCD
R
u8
1
30003
WatchDog s/w Version of XCD
R
u8
1
30004
Location string
R
string[12]
6
30010
ModBus slave ID
R
u8
1
30011
Monitor Status
R
u16
1
Upper byte : Function
Lower byte : Instrument Mode
30012
Inhibit current(mA)
R
u8
1 20 means 2.0mA
30013
Reserved
R
u16
1
30014
Active Alarm
R
u32
2 bit 0 Alarm 1 is active
bit 1 Alarm 2 is active
30016
Latched Alarm
R
u32
2 bit 0 Alarm 1 is active
bit 1 Alarm 2 is active
30018
Active Fault
R
u32
2
Upper Byte: fault
Lower Byte:warning
Bit 0:W1~Bit 6:W6
Bit 7:F1~Bit 11:F5
30020
Latched Fault
R
u32
2
Upper Byte: fault
Lower Byte:warning
Bit 0:W1~Bit 6:W6
Bit 7:F1~Bit 11:F5
40001
Systern ID code
R
u16
1
Upper Byte : Type Code : 0x25
Lower Byte : My Address
40002
Systern ID code
R
u16
1
Upper Byte : Type Code : 0x25
Lower Byte : My Address : Dummy Spacer
40003
Gas reading
R
f32
2
40005
Fault and Warning
R
u8
1 Fault = 1100 + Number
Warning = Number as is
40006
Alarm, fault and warning state
R
u8
1
bit 0 Alarm 1 is active
bit 1 Alarm 2 is active
bit 2,3 for future expansion
bit 4 Warning is active
bit 5 Fault is active
bit 6,7 for future expansion
Note: Latching relay setting latches Modbus
values in register 40006.
40007
Monitor state monitering
R
u8
1
1 : Normal
2 : Warm Up after power on
3 : Inhibit
12 : Calibration
40008
Reserved
R
u16
1
40009
Ca libration Due
R
f32
2
40011
Measuring Unit
R
u8
1
4 : PPM
3 : %Vol
5 : %LEL
1 : mg/m3
40012
Peak Reading
R
f32
2 Peak Reading
40014
Reserved
R
u16
3
40017
Temperature (
o
C)
R
s16
1
40018
Reserved
R
u16
28
40046
Measuring Gas name string
R
string[14]
7
40053
Reserved
R
s16
1
40054
Temperature (
o
F)
R
s16
1
40055
Reserved
R
u16
1
40056
Relay Status
R
u8
1 1 : Energized, 0 : De-energized
40057
Power Supply
R
f32
2
40059
Calibration Interval
R/W
u16
1
40060
Alarm Type
R/W
u8
1
High nibble : Alarm 2 Type
Low nibble : Alarm 1 Type
0: Disable, 1: Rising, 2:Falling
40061
Inhibit timeout
R/w
u16
1
40062
Relay configuration
R/w
u8
1
Bit: 0 ~ 2: Relay Type1 ~ Relay Type3
Bit: 3~5 : Relay Sstatus1 ~ Relay Status 3
Bit: 6 : Relay Latch Status
Summary of Contents for Sensepoint XCD RFD
Page 1: ...Technical Handbook Sensepoint XCD RFD Remote Flammable Detector ...
Page 65: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 65 China PA Certification ...
Page 66: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 66 18 2 Korea KTL ...
Page 68: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 68 ATEX for Sensor ...
Page 70: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 70 IEC Ex for Sensor ...
Page 79: ...www norrscope com ...