Gas detection systems for industrial environments 

1/8

 

 

 

 

 

 

Sensigas

®

 

Oxygen detectors 

ATEX 

II 3G  Ex nA nC d IIC T6 Gb certified 

 

URS20SS 

 

 

 

 

 

 

 

 

 

Sssssss 

 

 

 
11…28Vdc power supply. 
Electrochemical cell sensor designed for the detection of oxygen (O

2

). 

Up to three alarm thresholds plus sensing element fail. 

LED on sensing element body to indicate operating status. 

Automatic countdown of sensor life. 

 

Use 

The URS20SS detectors are used to detect oxygen excess or deficiency in hazardous 
(classified) areas of industrial environments and thermal power stations. 

An

 oxygen excess

 forms if it leaks in hospitals, laboratories, welding centres and, more 

in general, where oxygen is stored. 

Oxygen deficiency

 is an indirect measurement of the presence of other explosive or 

asphyxiant

 gases that deplete the oxygen in the air. 

URS20SS sensors can be used in stand-

alone mode with 4…20mA output or with an 

optional voltage-free contact relay card having the following four digital outputs: 

- Pre-alarm, 1

st

 alarm threshold, 2

nd

 alarm threshold, sensor fail. 

Operation 

If there is a gas leakage, the detector compares the measured concentration value with 
the  threshold  limit  setpoints  and  energises  the  associated  relays.  Information  on  the 
measured concentration value is always at the 

4…20mA output. 

Ordering 

To order, simply state the part number: 

URS20SS

For special versions, on request, please contact Customer Service. 

 

Summary of Contents for EsiWelma Sensigas URS20SS

Page 1: ...eaks in hospitals laboratories welding centres and more in general where oxygen is stored Oxygen deficiency is an indirect measurement of the presence of other explosive or asphyxiant gases that deple...

Page 2: ...umption mode applications at 1 or 2 thresholds 4 20mA Output reference selection 4mA 0 O2 20mA 30 O2 0mA no alarm 10mA 1st threshold alarm 20mA 2nd threshold alarm by jumper selectable polarity 4 20mA...

Page 3: ...nstructions for location of the detectors The detectors must be installed 1 where accidental gas leakages are possible 2 at least 1 5m away from heat sources or from vent holes 3 not in spaces where v...

Page 4: ...n order to change the default settings switch off the power supply input the new settings at the JP2 jumper circuit or at the S1 DIP switch as shown in the diagram then power up again in particular Th...

Page 5: ...Step 1 Insert the connection slot provided with the relay card into the control card making sure the flexible tab is towards the main terminal board Find CN3 connector CN3 connector Connection slot fl...

Page 6: ...on The sensors are factory calibrated so they normally do not require any other calibration once installed Still after installation an operational check of the sensors is recommended The detector will...

Page 7: ...return the sensor concerned to the supplier installer who in turn will send it back to the manufacturer Sensors may need to be re calibrated using the TUL40 calibration kit and the TUS40 20 handheld t...

Page 8: ...gas vapours flammable mist Ex nA nC d IIC T6 Gb Types of protection complying with EN60079 0 and EN60079 15 sensor body with type of protection d in compliance with EN60079 1 BVI 07 ATEX 0033 Type exa...

Reviews: