Navim Group Company EsiWelma Sensigas URS20SS Quick Start Manual Download Page 5

 

EW0826A4_en - rev. A 

Oxygen detectors 

 URS20SS 

05/10/2020 

Gas detection systems for industrial environments 

5/8

 

 

Mechanical installation 
of the optional relay 
card 

The  control  card  can  be  expanded  with  a  relay  card  inserted  into  a  dedicated 
connector 

CN3

  with  four  SPDT  relays  that  will  be  activated  under  the  following 

conditions:  pre-alarm,  1

st

  threshold  alarm  2

nd

  threshold  alarm  and  sensor  fail,  and 

relative LED alerts. 
To install the card, follow the instructions below: 
 
 

Step 1: 

Insert  the  connection  slot  provided 
with  the  relay  card  into  the  control 
card,  making  sure  the  flexible  tab  is 
towards the main terminal board. 
Find CN3 connector. 

 

 

CN3 connector 

 

Connection slot 
(flexible tab) 

 
 
 
 

 

Step 2: 

Fit  the  relay  card  snugly 
and pull the flexible tab of 
the 

connection 

slot 

towards the main terminal 
board. 
 
 
 
 
 

Flexible tab 

 
 
 

 

 
 

Step 3: 

Check  the  position  of  the  card.  Make  sure 
that  all  the  card  pins  fit  into  the  CN3 
connector and push slightly upwards to check 
that  the  flexible  tab  on  the  connection  slot 
keeps the card in place. 
 
 
 
 
 

 
 
Step 4: 

Tick  the  check  box  with  a 
permanent 

marker 

to 

indicate the presence of the 
relay card in the device 
 

 

 

 

 2,5 W 

TYPE URS20SS 

Summary of Contents for EsiWelma Sensigas URS20SS

Page 1: ...eaks in hospitals laboratories welding centres and more in general where oxygen is stored Oxygen deficiency is an indirect measurement of the presence of other explosive or asphyxiant gases that deple...

Page 2: ...umption mode applications at 1 or 2 thresholds 4 20mA Output reference selection 4mA 0 O2 20mA 30 O2 0mA no alarm 10mA 1st threshold alarm 20mA 2nd threshold alarm by jumper selectable polarity 4 20mA...

Page 3: ...nstructions for location of the detectors The detectors must be installed 1 where accidental gas leakages are possible 2 at least 1 5m away from heat sources or from vent holes 3 not in spaces where v...

Page 4: ...n order to change the default settings switch off the power supply input the new settings at the JP2 jumper circuit or at the S1 DIP switch as shown in the diagram then power up again in particular Th...

Page 5: ...Step 1 Insert the connection slot provided with the relay card into the control card making sure the flexible tab is towards the main terminal board Find CN3 connector CN3 connector Connection slot fl...

Page 6: ...on The sensors are factory calibrated so they normally do not require any other calibration once installed Still after installation an operational check of the sensors is recommended The detector will...

Page 7: ...return the sensor concerned to the supplier installer who in turn will send it back to the manufacturer Sensors may need to be re calibrated using the TUL40 calibration kit and the TUS40 20 handheld t...

Page 8: ...gas vapours flammable mist Ex nA nC d IIC T6 Gb Types of protection complying with EN60079 0 and EN60079 15 sensor body with type of protection d in compliance with EN60079 1 BVI 07 ATEX 0033 Type exa...

Reviews: