CONFIGURATION PARAMETERS
Using the ZM7601 or ZM7603 Configuration Tool Software, it is possible to program variables that affect control of the
variable air volume system. The variables that may be programmed and a brief description are listed below.
Recommended
Variable Name
Variable Label
Functional Description/Program Options
Value
Number of Fan Stages
FAN_STG
Only one fan stage is available.
1
Type of Supply and
FAN_TYPE
VAV fan actuator type.
Return Fans
0 = Modulating fan control of inlet vanes
or variable speed drive.
1 = Floating fan control.
2 = Velocity pressure control (2-speed fan).
Fan Motor Speed
FAN_MOTOR_SPEED
Programmable duration, in number of
seconds, for full motor travel from 0-100%.
Range = 30-160 seconds programmed to
specified motor speed; i.e., 60.
Default = 100 seconds.
Supply Fan Start Delay
FANSTART_DELAY
Prevents fan start-up after power-up or reset
60-90
condition. Valid if VN_CSD is not configured.
seconds
Value should equal number of seconds for full
supply fan motor travel. One second accuracy,
0-255 seconds.
Type of Cooling
COOL_TYPE
Programmable:
Equipment
0 = Staged cooling.
1 = Stages plus floating.
2 = 1 stage plus modulating cooling valve.
Number of Cool Stages
COOL_STG
Programmable cool stages 0-12 (total
compressors and unloaders).
Cooling Modulation
MOD_COOL_DELAY
Time delay between cooling on/off stages
30 seconds
Delay
and cooling modulation. Fifteen second
accuracy, 0-180 seconds.
Cool Motor Speed
COOL_MOTOR_SPEED
Programmable duration, in number of
seconds, for full motor travel from 0-100%.
Range = 30-160 seconds, programmed to
specified motor speed; i.e., 60.
Default = 100 seconds.
Compressor Number
COMP_NUM[ ]
Compressor/unloader array for configuration
Array
of cooling equipment. Compressors =
1, 2, 3, 4 and unloaders = 0; for example,
array: 6 stages, 2 compressors, 2 unloaders
per compressor programmed as:
Comp_Num [1] = 1
Comp_Num [2] = 0
Comp_Num [3] = 0
Comp_Num [4] = 2
Comp_Num [5] = 0
Comp_Num [6] = 0
Compressor Minimum
COOL_TIME
Value used for minimum on and off time
240 seconds
Time
with each compressor stage and for interstage
time delay. Fifteen second accuracy, 0-3780
seconds.
Unloader Minimum
UNLOAD_TIME
Value used for minimum on and off time
120 seconds
Time
with each unloader stage and for interstage
time delay. Fifteen second accuracy, 0-3780
seconds.