63-4309—2
30
VAV CONFIGURATION PARAMETERS (continued)
Control
Value
Control
Dependent
Dependent
Number
Variable Required
Required
Number
Variable Required
Value Required
ECONOMIZER (continued)
[CV] ECON_SELECT
0, 1, 2, or 3
See below.
0 to disable
None
N/A
With 1, 2, or 3
[CV] ECONO_TYPE
1 or 2
With 1
149
[DI] OD_ENT
Must be
configured.
With 2
[SP] WTR_ECONO_SP
30
°
to 100
°
F
3
[AI] CNDTMP
Must be
configured.
With 3
[CV] ECON_SENS1 & 2
Two AI control
numbers
AI XX
[AI] For ECON_SENS1
Must be
configured.
AI XX
[AI] For ECON_SENS2
[CV] ECON_OFFSET
0
°
to 100
°
F
WARMUP CONTROL
[CV] WARMUP_TYPE
0, 1, or 2
See below.
0 to disable
None
N/A
With 1 or 2
[SP] PRG_WARM_SP
30
°
to 90
°
F
[CV] HEAT_STG
1-6
[CV] AUTO_CHANGE
0 or 1
[CV] HEAT_HYSTERESIS
0
°
to 10
°
F
With 1
7
[AI] RA_TMP
Must be
configured.
With 2
4
[AI] SP_TMP
OCCUPIED/UNOCCUPIED CONTROL
[CV] SETBACK_TYPE
0, 1, or 2
See below.
0 to disable
None
N/A
With 1 or 2
[SP] PRG_NSB_SP
30 to 90
°
F
160
[DI] DAY_NT or
Must be
161
[DI] NTWRK_OCC_FLAG or configured.
[SP] RTC OCC/UNOCC
[CV] HEAT_STG
1-6
With 1
7
[AI] RA_TMP
Must be
configured.
With 2
4
[AI] SP_TMP
OPTIONAL
[CV] AIR FLO
0-255 seconds
157
[DI] AIR FLO
Must be
configured.
[CV] COND_DELAY
0-255 seconds
128
[DI] CND FLO
214
[DO] CNDPMP
[CV] LO_DA_LIM
10
°
to 50
°
F
[CV] LO_DA_DUR
0-765 seconds
1
[AI] DA_TMP
Must be
configured.
[CV] FANSTART_DELAY
0-255 seconds
163
[DI] VN_CSD
[CV] DEB_TIME0
0-255 seconds
128
[DI] CND FLO
[CV] DEB_TIME1
0-255 seconds
129
[DI] HP1
PM7600B
PM7600B INPUT AND OUTPUT OPTIONS