45
63-4309—2
PM7600B
PROGRAMMING
DA_TMP 70.00F MON 12;45A UNOCC 'ALARM"
PRESS =3.57 INW S_VEL +35.89 FPM
Run Screen (Normal Operation)
Run Screen (Alarms in History)
DA_TMP 70.00F MON 12;45A UNOCC 'ALARM"
PRESS =3.57 INW V_PRES +35.89 FPM
RUN SCREEN
PROGRAM
Program Access Menu (Press Program)
IF ACCESS
CODE IS
0 0 0 0
IF ACCESS
CODE IS NOT
0 0 0 0
ENTER NEW ACCESS CODE *
more 0 0 0 0
ENTER ACCESS CODE
more 0 0 0 0
PROGRAM: SETPOINT TOD UNITS *
more
TEMPERATURE PRESSURE RESET VELOCITY *
more
DA COOL SETPOINT CONTROL BAND *
more +70F +2F
DA HEAT SETPOINT CONTROL BAND *
more +65F +4F
WARMUP SETPOINT *
more +68F
SETBACK SETPOINT *
more +60F
ECONOMIZER MIN POS OFFSET IAQ MIN POS *
more 10% +8F 3-%
MA PREHEAT SETPT CRTL BAND OA LOCKOUT *
more +55F +6F +5oF
MIXED AIR LIMITS HIGH LOW *
end +90F +40F
SUPPLY STATIC PRES SETPT CTRL BAND *
more +3.5INW +2.0INW
RETURN CFM % OF SUPPLY CRTL BAND *
more 80.00% 6.00%
RETURN STATIC LIMITS HIGH LOW *
end +3.0INW -1.0INW
COOL RESET: SETPOINT START END *
more 60F +65F +70F
HEAT RESET: SETPOINT START END *
end +100F +65F +70F
VELOCITY MINIMUM LIMIT TIME DELAY *
more +180.5FPM +60.0SEC
LO TO HI SPEED FAN: SWITCH HYSTERESIS *
more +300.0FPM +60.1FPM
HI TO LO SPEED FAN: TIME DELAY *
end +60.0SEC
TOD: SCHEDULES EQUIPMENT HIOLDAYS CLOCK *
more
SCH1 OCC UNOCC OCC UNOCC
more 24 HR UNOCCUPIED
SCH2 OCC UNOCC OCC UNOCC
more 24 HR OCCUPIED
SCH32 OCC UNOCC OCC UNOCC
more 11:20 A 11:50A 12:10 P 12:30P
32 POSSIBLE
SCHEDULES
EQU SCH#5 OCC UNOCC OCC UNOCC
more SUN 10:20A 11:20A 12:20P 12:50P
EQU SCH#5 OCC UNOCC OCC UNOCC
more MON 10:20A 11:20A 12:20P 12:50P
EQU SCH#5 OCC UNOCC OCC UNOCC
more TUE 10:20A 11:20A 12:20P 12:50P
EQU SCH#5 OCC UNOCC OCC UNOCC
more WED 10:20A 11:20A 12:20P 12:50P
EQU SCH#5 OCC UNOCC OCC UNOCC
more THU 10:20A 11:20A 12:20P 12:50P
EQU SCH#5 OCC UNOCC OCC UNOCC
more FRI 10:20A 11:20A 12:20P 12:50P
EQU SCH#5 OCC UNOCC OCC UNOCC
more SAT 10:20A 11:20A 12:20P 12:50P
EQU SCH#5 OCC UNOCC OCC UNOCC
more SP1 10:20A 11:20A 12:20P 12:50P
EQU SCH#5 OCC UNOCC OCC UNOCC
more SP2 10:20A 11:20A 12:20P 12:50P
EQU SCH#5 OCC UNOCC OCC UNOCC
more SP3 10:20A 11:20A 12:20P 12:50P
EQU SCH#5 OCC UNOCC OCC UNOCC
more SP4 10:20A 11:20A 12:20P 12:50P
DISPLAY METRIC (S) UNITS
end NO
PRESS CLEAR TO DELETE A HOLIDAY
(IN PROGRAM MODE ONLY)
HOLIDAY START DATE END DATE DAY SCH
more MAY 25 1991 MAY 25 1991 SP4
HOLIDAY2 START DATE END DATE DAY SCH
more JULY 4 1991 JULY 4 1991 SP4
24 POSSIBLE
HOLIDAYS
HOLIDAY START DATE END DATE DAY SCH
more NOV 23 1991 NOV 25 1991 SP2
DISPLAY CLOCK ON RUN SCREEN
more YES
SET: TIME DATE FORMAT
more 10:50A SEP 20 91 12 HR
DAYLIGHT SAVINGS ENABLE TIME BASE
more YES 50-60HZ
DAYLIGHT SAVINGS MONTH DOW WEEK
more START APR SUN 1
DAYLIGHT SAVINGS MONTH DOW WEEK
more END OCT SUN 5
Pressure Gains (Hidden/Special)
Temperature Gains (Hidden/Special)
SUPPLY PRESSURE: p_kd p_kp p_ki
more
+4.356 +.0035 +9.762
RETURN CFM: p_kp p_ki
more +.0035 +9.762
TEMPERATURE: t_kd t_kp t_ki
more +1.356 +.7035 +4.762
REHEAT: t_kp t_ki
more +.7035 +4.762
CONFIRM: CLEAR PROGRAMMEMORY?
+ = YES ANY OTHER KEY = NO
M4142A
PM7600B
PM7600B PROGRAMMING SUMMARY
For programming and reviewing data, use the S7600 Keyboard
Display Module. The S7600 displays English language words
on a 6" wide screen. These words are arranged in "menues."
By pressing the keys located under the screen, selections
can be made front the menues (similar to most computer software).
These selections include reviewing load status and entering
programs.
The 13 keys on the front of the S7600 allow the user to quickly
and easily move through menus, reviewing and modifying
programs.
+
-
When in Program Mode Main Menu, pressing and
keys simultaneously will display the HIDDEN SCREEN
First, select the main function to be performed (PROGRAM,
REVIEW, BYPASS, or RUN) by pressing the desired key. To
modify data using the PROGRAM mode ot to BYPASS, a
security access code must be entered - no security access is
required for a REVIEW or RUN.
Notice the cursor line under the first line of a word in the
menu. The position of this cursor indicates the user's choice
from the menu.
To move the cursor to another choice, press the or key.
To move to the next menu, press the key.
To move to the previous menu, press the key.
To modify data, press or key.
+
-
4 keys for SELECTING main functions
4 keys for MOVING from one menu to another
2 keys for MODIFYING data
3 keys for PERFORMING special functions
PROGRAM
REVIEW
BYPASS
RUN
ALARM
SILENCE
CLEAR
FAST
+
-