17
63-4309—2
Return High Static
RET_STATIC_
Return Air Flow High Static Limit, in inches water
2.0
Pressure Limit
HI_LIM
column (in. wc). Will shut down fan upon sensing
excessively high pressure. Available range is 0.0
to 10.0 in. wc. Applicable to PM7600B,
Version 2.0 or later.
Return Low Static
RET_STATIC_
Return Air Flow Low Static Limit, in inches water
-2.0
Pressure Limit
LO_LIM
column (in. wc). Will shut down fan on sensing
excessively low pressure. Available range is -5.0 to
5.0 in. wc. Applicable to PM7600B,
Version 2.0 or later.
Return Fan Vane
RET_FAN_
Return Fan Vane Motor Speed. Available range is
Motor Speed
MOTOR_SPD
0 to 255 seconds. Applicable to PM7600B,
Version 2.0 or later.
Return Fan
RET_FAN_CB
Return Fan Control Band Available range is 0 to
5%
Control Band
100% of Supply Fan Air Flow.
Applicable to PM7600B, Version 2.0 or later.
Mixed Air Preheat
MA_PRE_HT_SP
Mixed Air Preheat Set Point, used to control the
55
°
F
Setpoint
Preheat Coil. Available range is 33 to 90
°
F.
Applicable to PM7600B, Version 2.0 or later.
Preheat Control
PRE_HT_CB
Preheat Control Band. Available range is 0 to 20
°
F.
6.0
Applicable to PM7600B, Version 2.0 or later.
Mixed Air High
MA_HI_TMP_LIM
Mixed Air High Temperature Limit, for Alarm only,
100
Temperature Limit
no shutdown. Applicable to PM7600B,
Version 2.0 or later.
Mixed Air Low
MA_LO_TMP_LIM
Mixed Air Low Temperature Limit, for Alarm and
40
Temperature Limit
fan shutdown. Available range is 33
°
to 90
°
F.
Applicable to PM7600B, Version 2.0 or later.
OA Temperature
OA_PRE_HT_
Outside Air Temperature above which Preheat is
45
Preheat Lockout
LOCKOUT
locked out. Available range is 0 to 90
°
F.
Applicable to PM7600B, Version 2.0 or later.
IAQ Economizer
IAQ_ECON_
Economizer Minimum Position on receipt of IAQ
30
Minimum Position
MIN_POS
Digital Input in % Open. Available range is 0 to
100%. Applicable to PM7600B, Version 2.0 or later.
Return Fan
RET_KP
Return Fan Proportional Gain.
1
PI Gains
Range 0 to 10.
RET_KI
Return Fan Integral Gain.
1
Range 0 to 10.
Applicable to PM7600B, Version 2.0 or later.
Preheat
PRE_KP
Preheat Proportional Gain.
1
PI Gains
Range 0 to 10.
PRE_KI
Preheat Integral Gain.
1
Range 0 to 10.
Applicable to PM7600B, Version 2.0 or later.
SETPOINT PARAMETERS (continued)
Rec-
ommended
Variable Name
Variable Label
Functional Description/Program Options
Value
PM7600B
PM7600B INPUT AND OUTPUT OPTIONS