63-4309—2
20
Compressor 2 Oil Pressure
OIL_F2
138
As with OIL_F1, lock out Compressor 2.
Compressor 3 Oil Pressure
OIL_F3
139
As with OIL_F1, lock out Compressor 3.
Compressor 4 Oil Pressure
OIL_F4
140
As with OIL_F1, lock out Compressor 4.
Low Pressure 1 Safety
LP1
141
OFF w/LLSV OFF=
Normal operation if compressor off.
OFF w/LLSV ON=
Compressor operation during startup
time delay if LP delay selected. If
delay is exceeded, turn off Compres-
sor 1, turn on alarm digital output and
send alarm message to S7600. Control
without Compressor 1.
ON w/LLSV OFF =
Compressor on for pump out time de-
lay. If delay is exceeded, turn off Com-
pressor 1, turn on alarm digital output
and send alarm message to S7600.
ON w/LLSV ON =
Normal operation with compressor on.
NOTE: The W7600 must be reset if a Low Pressure
Failure occurs in start-up or normal operation.
Low Pressure 2 Safety
LP2
142
Operation as with LP1.
Low Pressure 3 Safety
LP3
143
Operation as with LP1.
Low Pressure 4 Safety
LP4
144
Operation as with LP1.
DIGITAL INPUTS (continued)
S7600
W7600 Input
Point Name
Label
Control Number
Functional Description
PM7600B
PM7600B INPUT AND OUTPUT OPTIONS
Compressor 1 Shed
SHED_1
145
INACTIVE =
Normal operation.
ACTIVE =
Disable Compressor 1.
Compressor 2 Shed
SHED_2
146
INACTIVE =
Normal operation.
ACTIVE =
Disable Compressor 2.
Compressor 3 Shed
SHED_3
147
INACTIVE =
Normal operation.
ACTIVE =
Disable Compressor 3.
Compressor 4 Shed
SHED_4
148
INACTIVE =
Normal operation.
ACTIVE =
Disable Compressor 4.
Outdoor Air Enthalpy
OD_ENT
149
INACTIVE =
Economizer enable.
High
ACTIVE =
Economizer disable.
Dirty Filter
FILTER
150
INACTIVE =
Normal operation.
ACTIVE =
Turn on alarm digital output and send mes-
sage to S7600. Does not stop fan if dirty filter
occurs.
NOTE: Not monitored if fan is off.
System Switch On
SYS_SW
151
INACTIVE =
Disable W7600 control.
ACTIVE =
Enable W7600 control.
Alarm Silence
AL_SIL
152
INACTIVE =
Normal operation.
ACTIVE =
Turn off alarm output; no annunciation.
Heat Failure
HT_FL
154
INACTIVE =
Normal operation.
ACTIVE =
Fan enabled; turn off and lock out heat. Turn
on alarm digital output and send alarm mes-
sage to S7600.
NOTE: The W7600 must be reset if a Heat Failure
occurs.
Fan Motor Safety
FN_FL
155
INACTIVE =
Normal position.
ACTIVE =
Turn on alarm digital output and send alarm
to S7600. Turn off all outputs and disable
control.
NOTE: Not monitored if fan is off.
NOTE: The W7600 must be reset if a Fan Motor
Safety Failure occurs.