Commissioning Manual
16.5 Hochiki Multi-Sensor Support
•
The Hochiki Multi-Sensor is supported as detailed below from panel software version 824 onwards.
Previously, from version 698, the multi-sensor was partially supported – operating as an optical smoke
device becoming more sensitive with temperatures above 40
°
C.
•
Where the control panel is in normal operation or sensitivity day mode is invoked, the multi-sensor
mode and threshold parameters can be modified according to the specific site requirements. This
allows a different mode of operation at different times of the day (see Section 11.3 Sensitivity Mode).
For each multi-sensor address, in the edit device menu, choose to ‘edit thresholds’. Firstly, the mode
of operation will be presented. Select 0 for multi-mode, 1 for optical-smoke only mode or 2 for heat
only mode. Normal threshold set-up will follow. These settings will take effect on a device by device
basis throughout the day mode period (where sensitivity mode is programmed).
•
Where night mode is invoked (as part of sensitivity day mode), the device operates in the multi-sensor
mode providing the control panel with an analogue value representing a combination of the smoke
and heat elements of the sensor. The pre-alarm threshold is fixed at 45 and the full-alarm threshold at
55.
16.6 System Sensor/ Morley-IAS Multi-Sensor & Laser Support
16.6.1 System Sensor/ M-IAS Multi & Laser Diagnostics
•
When viewing the device from the user menus, the meaning of the analogue value is as follows:
Value displayed
Multi
laser
0
No device
No device
1
Mid-range invalid
Mid-range invalid
2
Mid-range invalid
Mid-range invalid
3
Mid-range invalid
Mid-range invalid
4
Mid-range invalid
Mid-range invalid
4 or 7
Out of range
Out of range
5
Low chamber trouble
Drift alert 0.3%
10
Maintenance alert
Maintenance alert
15
Maintenance urgent
Drift alert 0.6%
20 initialising
Initialising
29 multi / 32 laser
Normal
Normal
50 multi / 50 laser
Level 1 alarm
Level 1 alarm
64 multi / 57 laser
Level 2 alarm
Level 2 alarm
79 multi / 64 laser
Level 3 alarm
Level 3 alarm
93 multi / 71 laser
Level 4 alarm
Level 4 alarm
107 multi / 79 laser
Level 5 alarm
Level 5 alarm
121 multi / 86 laser
Level 6 alarm (HEAT)
Level 6 alarm
- / 93 laser
-
Level 7 alarm
- / 100 laser
-
Level 8 alarm
- / 107 laser
-
Level 9 alarm
System Sensor Multi-sensor & Laser Diagnostics