ZX Fire Alarm Control Panels
MORLEY-IAS
Commissioning Manual
Document No. 996-175-000-1, Revision 01
Page 19
•
The Loop & Battery Calculator must be used to determine the maximum number of LEDs able to be turned
on in alarm.
[ Panel in Commissioning mode ]
---------------------------------------------
L1 Z003 A086 "RESEARCH ROOM 52 "Ev106
Ion Smoke + Signal= 26 (Inputs 2..0=LLH)
5.2.4.1
Changing Device Information
•
Changes are made by first pressing the ‘Change’ key. A menu of items that can be changed will
appear according to the type of device, For example.
•
An ionization smoke detector will allow changes on:
[ Panel in Commissioning mode ]
---------------------------------------------
1)Sensor Text
2)Zone
3)Event
4)Alarm thresholds 6)Action
8)Group
•
For Apollo protocol loops with Ancillary Sounder attached (or to be
attached or removed) to/from an ionization smoke detector will allow
changes on:
Page
1
[ Panel in Commissioning mode ]
---------------------------------------------
1)Sensor Text
2)Zone
3)Event
4)Alarm thresholds 6)Action
7)Sndr >>
Page
2
[ Panel in Commissioning mode ]
---------------------------------------------
<< 8) Group
To add or remove an ancillary sounder to this device, select ‘7) Sndr’ and respond to the prompt given.
•
A call-point will allow changes on:
[ Panel in Commissioning mode ]
---------------------------------------------
1)Sensor Text
2)Zone
3)Event
6)Action
8)Group
>>
Loop Zone Address
Location Text
Event
Device Type
Analogue Signal
Digital input status (Apollo only)
H=Logic High L=Logic Low
Ancillary Sndr
Attached
Indicator
For use with software
version 826 onwards