ZX Fire Alarm Control Panels
MORLEY-IAS
Commissioning Manual
Document No. 996-175-000-1, Revision 01
Page 13
4 Commissioning a New Installation
•
This section provides a guide to the steps that are required to commission a new installation.
•
Precise details on how to perform each step, and on the functionality of each programming option, are
given in appropriate sections of this manual.
4.1 Step 1 – General Setup
•
Ensure that the panel configuration memory is cleared and returned to factory settings. Refer to Time /
Date – System on Page 2 of the Commissioning Menus.
•
Select the ‘Setup options’ from Page 3 of the Commissioning Menus. Press ‘Yes’ to step through each
item to inspect the factory default settings and to make changes as required. For example, to enter
service telephone number and company name.
4.2 Step 2 – Configure Each Signalling Loop
•
Select the CONFIGURE option from Page 1 of the Commission Menus and then perform the
following.
1. Select ‘Signalling Loop 1’.
2. Perform an ‘Auto Learn’
3. Select ‘Devices’ and change sensor location text as required.
4. Assign
Zones.
•
Repeat actions 1-4 above for each signalling loop connected to the panel.
•
Enter Zone descriptions.
NOTE:
1. If using a PC to program the panel, actions 3 and 4 above will already have been defined on the PC.
2. When using ZX panel software version 826, or later, and the Apollo
protocol with ancillary sounders fitted, refer to Section 5.2.4.9.
3. When using ZX panel software version 834, or later, and Morley-IAS or
System Sensor protocol with ancillary LEDs fitted, refer to Section
5.2.4.10.
4.3 Step 3 – Configure Peripherals (if required)
•
Select the CONFIGURE option from page 1 of the Commission Menus and then perform the following.
1. Select
‘Peripheral’.
2. Perform an ‘Auto Learn’.
3. Select ‘Devices’ and change each unit’s location text as required.
4. Assign Zones and set the operation of the unit.
4.4 Step 4 – Configure Outputs (sounders and relays)
•
Select the CONFIGURE option from page 1 of the Commission Menus and then perform the following.
1. Select ‘Sounders’, if zoned ringing patterns are required and program accordingly.
2. Select ‘Relays’, if zoned operation is required and program accordingly.
For use with software
version 826 onwards
For use with software
version 834 onwards