MORLEY-IAS
ZX Fire Alarm Control Panels
Page 24
Document No. 996-175-000-1, Revision 01
Commissioning Manual
1. Fault
Closing the input produces a ‘warning’ message on the display. The common
‘Fault’ LED and the corresponding zone fault LED will also illuminate.
2. Zone
Fire
Closing the input puts the designated zone into fire. ‘True’ Break Glass Call
Points should ALWAYS be set to this option.
Note: With panel software prior to version 834 this was called ‘Fire’.
3. Bomb
Alert
Creates a ‘bomb alert’ from the designated zone. All sounders / relay outputs will
react according to their programming for this zone.
4. Class
Change
Closing the input forces all system sounders to ring. This condition is not
latched. Once the input opens again the sounders will stop ringing.
5. Security
Allows the input class ‘security alert’ to be configured.
6. Non-latch
1
Allows an input device to create a temporary system event that is cleared when
the input is restored to its normal condition. This option is not normally used on
fire systems. Contact technical support department for further information before
using this option.
7. Plant
Closing the input produces a ‘warning’ message on the LCD, but does not
illuminate the yellow fault LED’s.
8. Group
Disable
1
Allows an input device to disable a group of detectors remotely from the panel.
9. Confirmed
Fire
1
This input acts as an MCP and overrides any programmed delays to operate
configured outputs.
10. Panel Reset
1
This will reset the panel. Performs in the same way as the panel RESET key.
11. Evacuate
1
Will operate all configured outputs immediately.
12. Silence Alarms
1
Will de-activate all currently active outputs.
13. not used
Allows an input device to be turned off. Any action or state change at the input
will be ignored.
Table 6 – List of Device Actions
•
Press the Yes key once the desired option is shown. The display will then revert to the normal device
display, but will in addition show in the bottom right corner the alarm action of the input. For example:
[ Panel in Commissioning mode ]
---------------------------------------------
L1 Z056 A106 "PLANT CONTROL ROOM
"
I/O unit Signal= 16 Security
•
The display can also be placed in this ‘action display’ mode at any time by pressing the ‘6’ key when
viewing any device.
5.2.4.7 Class
Change
EN54
N/A
EN54-2
Class Change
•
The operation of a ‘Class Change’ input MUST be restricted to
LEVEL 2 ACCESS only. Install accordingly using a key switch to
activate or locate in a restricted area.
1
These are local to the panel only and are not broadcast across a network.