Page 26
Document No. 996-175-000-1, Revision 01
Commissioning Manual
•
Repeat the last 3 items above for each ancillary sounder fitted. Note that when you have added an
ancillary sounder to a device, the Text description displayed in the ‘Devices’ menu will be modified
such that a ‘+’(positive) sign will be appended to the description. This is used to indicate that the
device described has an ancillary sounder attached to it.
•
Note that to remove ancillary settings you must wipe the panel memory or download a new
configuration, with the device removed, or change the EEPROMs for a different software version.
Ancillary settings will persist across auto-learn operations.
5.2.4.10 Ancillary LED (Morley-IAS & System Sensor)
•
For the System Sensor and Morley-IAS protocol only with software version 834 onwards, the MI-MM3
micro-monitor module ancillary LED can be configured to activate as a ‘relay’.
•
Where MMI-MM3 micro-monitor devices have been fitted to appropriate devices on the loop, make
sure that you have noted the location /address of each device to which an ancillary LED has been
connected. From the control Panel, Commissioning menu:
1. Select the appropriate loop
2. Select ‘Devices’ menu
3. Select the address which has an ancillary LED attached
4. Select
‘Change’
5. Select ‘7) LED’ to add (or remove) an ancillary LED.
•
Repeat the last 3 items above for each ancillary LED fitted. Note that when you have added an
ancillary LED to a device, the Text description displayed in the ‘Devices’ menu will be modified such
that a ‘+’(positive) sign will be appended to the description. This is used to indicate that the device
described has an ancillary LED attached to it.
•
Note that to remove ancillary settings you must wipe the panel memory or download a new
configuration, with the device removed, or change the EEPROMs for a different software version.
Ancillary settings will persist across auto-learn operations.