2. Specifications - Technical and Operating Specifications
Revision 5
10260S HercuLine® Actuator Installation, Operation and Maintenance Manual
9
7/07
Specifications - Actuator with Digital Electronics
Electrical
Input Signals
Analog
: 0/4 to 20 mA
(With supplied shunt resistor for current range: 250 ohms ±0.1 %
Part Number: 070756)
0/1 to 5 Vdc
0 to 10 Vdc
Digital
: Modbus RTU RS485 (Remote setpoint)
Input Impedance
Input
0/4 to 20 mA
1 to 5 Vdc
Input Impedance
250 ohms
10 M ohms
Input
Characterization
Provides characterization of the input signal.
Selections are Linear, Square Root or Custom – Equal %, Quick Opening, User
Defined.
Sensitivity
0.2% to 5% of 90
°
span, proportional to deadband
Hysteresis
Less than 0.4% of full scale.
Deadband
0.2% to 5.0% of 90
°
span, adjustable. Shipped at 0.5% span.
Repeatability
0.2% of 90
°
span
Voltage/ Supply
Stability
0.25% of span with +10/–15% voltage change
Temperature
Coefficient
Less than
±
0.030% of span per degree C for 0 °C to 50 °C
Less than
±
0.05% of span per degree C for –30 °C to 75
°C
Zero Suppression
90 % of span
Input Filters
Selectable spike and low pass filters.
Solid State Motor
Control
Two triac switches for clockwise or counterclockwise motor operation.
Fail-safe Operation
If input signal exceeds configured input range. Selectable and adjustable.
Feedback Ssignals
0 to 20 mA, or 4 to 20 mA
0 to 5 Vdc, or 1 to 5 Vdc with 250 ohm resistor
±
0.1 %
0 to 16 Vdc with 800 ohm resistor
±
0.1 %
Slidewire Emulation
Provides output voltage ratiometric to shaft position and potentiometric to supply
voltage (1-18 Vdc) without a slidewire. Emulates a 100 to 1000 ohm slidewire. 10 mA
output maximum
Digital Input
Contact closure: 5 Vdc provided by actuator.
Power Isolation
Input and output signals are isolated from power.
Load Requirement
(4-20)
Current Out, - 0 to 1000
Ω
Diagnostics
Self-test diagnostics of RAM, SEE memory, Configuration and Calibration at power up.
Operation statistics recorded for predictive maintenance. See Maintenance Set Up
Group.