4. Set Up and Calibration Procedures - Input Set Up Group
Revision 5
10260S HercuLine® Actuator Installation, Operation and Maintenance Manual
37
7/07
Equal Percentage Valve Characteristic
Table 9 contains values that approximate an equal percentage valve characteristic in the actuator. When the
EQUL custom characterization type is selected, the values in Table 9 are automatically loaded into the
actuator configuration to produce the characteristic as presented in the graph. The Xn VAL is the input
value as a percentage of range and Yn VAL is the characterized output (actuator shaft position) as a
percentage of range.
Table 9 Equal Percentage Valve Characteristic Table
Order
Xn VAL
% of
Range
Yn Val
% of
Range
Equal Percentage Valve Characterization
0 0 0
1 5 0.8
2 10 2.1
3 15 3.2
4 20 4.9
5 25 6.5
6 30 8.4
7 35
10.7
8 40
13.2
9 45
15.7
10 50 18.7
11 55 22.6
12 60 27.2
13 65 33.4
14 70 40
15 75 46
16 80 53.8
17 85 63.2
18 90 73.7
19 95 86.2
20 100 100
10 20 30 40 50 60 70 80 90 100
Xn VAL - Actual Input
0