4. Set Up and Calibration Procedures - CAL POSOUT Group
Revision 5
10260S HercuLine® Actuator Installation, Operation and Maintenance Manual
55
7/07
CAL POSOUT Group
The CAL POSOUT group is used to verify that the position sensor is operating and adjusted properly. This
group allows the local display to indicate the output voltage of the position sensor PWA. This display is
used when verifying that the sensor is operating and that it is properly calibrated. Table 21 shows the
selections available for the CAL POSOUT group.
Table 21 CAL POSOUT Group Parameters
Lower Display
Prompt
Upper Display
Selections or
Range of Setting
Parameter Definition
CALPOS
n.nnn *
POSITION SENSOR OUTPUT
—
Read Only.
Displays the
output voltage of the position sensor PWA
To access the display…
Press
Result
SETUP
until you see
Upper Display
=
CAL
Lower Display
=
POSOUT
FUNCTION
Upper Display
=
DIS
Lower Display
=
CALPOS
or
key
Upper Display
=
BEGN
Lower Display
=
CALPOS
FUNCTION
Upper Display
=
n.nnn
(Sensor output in volts)
Lower Display
=
POSOUT
Auto - Manual Drive Switch
The Auto - Manual switch is located on the side of the actuator case below the handwheel. The switch
allows manual mode control of the actuator motor for set up, calibration and troubleshooting. Figure 16
shows an illustration of the Auto - Manual switch and Table 22 describes the switch settings. The Auto -
Manual Drive switch setting overrides all input signals (analog signal and remote setpoint) and local
display mode settings.