4. Set Up and Calibration Procedures - Local Display and Keypad
Revision 5
10260S HercuLine® Actuator Installation, Operation and Maintenance Manual
29
7/07
Table 4 Keypad Description
Key or
LED Indicator
Function
SET UP
Places the actuator in the set up group select mode. Sequentially displays set up
groups and allows the FUNCTION key to display function parameters within the set
up group.
See for descriptions of the various options available in the set up groups.
FUNCTION
Used in conjunction with the SET UP key to select the individual functions of a
selected configuration set up group.
Used during field calibration procedure.
MAN/AUTO
Alternately selects:
MAN
- Actuator is in Manual mode.
AUTO
- Actuator is in Automatic mode.
NOTE: When in Manual mode the POS display is automatically selected so you
can use the up and down arrow keys to drive actuator motor manually.
DISPLAY
Pressing this key repeatedly cycles through the operating parameters that can be
shown on the lower display.
INP –
Input. Shows the value of the actuator input.
OP
–
Output. Shows the value of the actuator output
DE –
Deviation. Shows deviation between input value and actuator position.
POS –
Position. Shows current actuator position.
Increases the configuration values shown on the display. Also shown as
.
In manual mode and POSition display selected, pressing this key will drive actuator
motor in direction of increasing signal input.
Decreases the configuration values shown on the display. Also shown as
.
In manual mode and POSition display selected, pressing this key will drive actuator
motor in direction of decreasing signal input.
☼
Indicates the movement of the actuator arm in the counterclockwise direction.
NOTE: Actuator rotation is the direction of the output shaft when facing the end of
the shaft and refers to the direction of rotation on increasing signal.
☼
Indicates the movement of the actuator arm in the clockwise direction.
NOTE: Actuator rotation is the direction of the output shaft when facing the end of
the shaft and refers to the direction of rotation on increasing signal.
☼
STALLED
Indicates that the actuator has detected a motor stall condition.
☼
ALARM
Indicates a programmed alarm condition exists.
☼
MANUAL
Indicates actuator is in manual mode. On solid when placed in manual mode from
the local display mode key. Blinks at a 1 sec rate when placed in manual mode
from the external drive switch.
☼
AUTO
Indicates actuator is in automatic mode.
Summary of Contents for HercuLine 10260S
Page 10: ......
Page 94: ......
Page 121: ......
Page 122: ...Honeywell Field Solutions Honeywell Inc 512 Virginia Drive Fort Washington PA 19034 ...