4. Set Up and Calibration Procedures - Input Set Up Group
Revision 5
10260S HercuLine® Actuator Installation, Operation and Maintenance Manual
35
7/07
Lower Display
Prompt
Upper Display
Selections or
Range of Setting
Parameter Definition
Direct
CCW
[default]
or
CW
ACTUATOR ROTATION
—This selection determines the
direction of rotation of the actuator shaft.
Counterclockwise
rotation
Clockwise
rotation
NOTE: Actuator rotation is the direction of the output shaft
when facing the end of the shaft and refers to the direction of
rotation on increasing signal.
Dband
0.2
to
5.0
(in percent of
span)
default = 0.5
INPUT DEADBAND
—Specifies an adjustable gap that is the
difference between the setpoint value and the value at which
the motor energizes. Deadband is set in percent of full span.
FSFTYPH
LAST
UP
DOWN
USER
default = UP
FAILSAFEHI TYPE
—Selects the motor position you want
the actuator to go to when input signal is above the high end
range value.
NOTE: Failsafe condition occurs when the input exceeds its
high end range value by 3%,
Last Position
—Actuator motor remains at last position.
Up
—Actuator motor moves to full scale value.
Down
—Actuator motor moves to zero value.
User selected value
—Actuator motor moves to a customer-
defined value.
*
Allows setting of failsafehi input value.
FsFVALH *
0
to
100%
default = 100
FAILSAFEHI INPUT VALUE
—(FailsafeHI Type USER only)
Selects the motor position you want the actuator to go to
when input signal is above the high end range value.
Range is from 0 to 100%.
FSFTYPL
LAST
UP
DOWN
USER
default = DOWN
FAILSAFELO TYPE
—Selects the motor position you want
the actuator to go to when input signal is below the low end
range value or on loss of input signal.
NOTE: Failsafe condition occurs when the input exceeds its
low end range value by 3%, or when the input signal goes to
zero. For input types 0 to 20mA, 0 to 5 V, and 0 to 10 V
there is no failsafe condition at the zero value.
Last Position
—Actuator motor remains at last position.
Up
—Actuator motor moves to full scale value.
Down
—Actuator motor moves to zero value.
User selected value
—Actuator motor moves to a customer-
defined value.
*
Allows setting of failsafelo input value.