– 32 –
Output Relay Module
PROMPT
EXPLANATION
01 SUPERVISED CF?
0
If you selected device type 04 (relay module), this prompt appears. Enter
1
if the unit is a 4204CF. If not,
enter
0
. If you enter 1, only Relay 1 (Output A) and Relay 3 (Output B) on each module may be programmed
for functions.
NOTE:
For Commercial Fire installations, only one notification appliance module may be used, and only one
notification appliance output (A or B) may be used on that module.
Press [
✱
] to accept entry.
Communicator
If you selected device type 6, the 6160 and 6160CR-2 Keypad functions similarly to the 7720P Programming Tool. See
Figure
1 for the functions of the keys on the 6160CR-2.
6160
1
OFF
4
MAX
7
INSTANT
READY
2
AWAY
5
TEST
8
CODE
0
3
STAY
6
BYPASS
9
CHIME
#
SILENCED
TROUBLE
ALARM
SUPV
POWER
6160CR2-001-V0
ARMED
READY
6160CR-2
NOTE: The 6160CR-2 must be used in Commercial
Fire installations
Figure 1: 6160CR-2 Key Functions for Programming the Communicator
Each key has two possible functions: a normal function and a SHIFT function. To perform a normal key function, simply press
the desired key. To perform a SHIFT key function, press SHIFT key, then press desired function key.
Normal and SHIFT key Functions:
Key
Normal Key Function
SHIFT Key Function
BS/ESC
[BS]: Press to delete entry
[ESC]: Press to quit Program Mode
Also, can reset EEPROM defaults *
↓
/
↑
[
↓
]: Scroll down programming
[
↑
]: Scroll up programming
N/Y
[N]: Press for "NO" answer
[Y]: Press SHIFT-Y for "YES" answer
SHIF
T
Press before pressing a SHIFT key function. Will light READY LED. LED goes out once a key is
pressed. Press again for each SHIFT function desired.
1/A
[1]: For entering the number 1
[A]: Used for entering C.S. ID number
2/B
[2]: For entering the number 2
[B]: Used for entering C.S. ID number
3/C
[3]: For entering the number 3
[C]: Used for entering C.S. ID number
4/D
[4]: For entering the number 4
[D]: Used for entering C.S. ID number
5/E
[5]: For entering the number 5
[E]: Used for entering C.S. ID number
6/F
[6]: For entering the number 6
[F]: Used for C.S. ID & FAST Mode
7/S
[7]: For entering the number 7
[S]: Press to display diagnostic status
8/T
[8]: For entering the number 8
[T]: Press to send TEST messages
9/X
[9]: For entering the number 9
[X]: Press to reset the 7845i-ent
*/SPACE
[*]: Not used with 7845i-ent
[SPACE]: Not used with 7845i-ent
0
[0]: For entering the number 0
No SHIFT function
#/ENTER
[#/ENTER]: Press to accept entries
No SHIFT function
*
Active only when the "REVIEW?" prompt is displayed.
Summary of Contents for Ademco VISTA-32FB
Page 58: ... 58 NOTES ...
Page 59: ... 59 NOTES ...
Page 60: ... 60 NOTES ...
Page 61: ... 61 NOTES ...
Page 62: ... 62 NOTES ...
Page 63: ... 63 NOTES ...