–2–
Table of Contents
Programming Field Settings for UL864 Compliance 2
Recommended Programming Procedure................. 6
Program Field Index ................................................. 7
VISTA-32FB Programming Form ............................. 8
Partition-Specific Fields.......................................... 14
Programming With #93 Menu Mode ...................... 16
5800 Series Transmitters Loop Designations ........ 20
Alpha Descriptor Vocabulary.................................. 30
Relay Voice Descriptors and Custom Word
Substitutes Vocabulary........................................ 39
System Layout Worksheets.................................... 40
Output Devices Worksheets ................................... 47
Scheduling Menu Prompts ..................................... 53
Scheduling Worksheets.......................................... 54
Programming Field Settings for UL864 Compliance
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED
PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements
in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features
or options must be limited to specific values or not used at all as indicated below.
Program feature or option Permitted in
UL864? Y
/N
Possible settings
Settings permitted in UL 864
✱
08 TEMPORAL SIREN
PULSE
N
0 = disable
1 = enable
Not used at this time. Must be set to
“0” (disable)
✱
13 ALARM SOUNDER (BELL)
TIMEOUT
Y
Enter 01-15 multiplied by 2 minutes.
00 = no timeout.
Must be set to “3” (Minimum of 6
minutes).
✱
17 AC LOSS KEYPAD
SOUNDING
N
0 = disable
1 = enable
Must be set to “1” (enabled).
✱
20 VIP MODULE PHONE
CODE
N
Enter 01 - 09 for the first digit; enter
11 for “*” or 12 for “#” for the second
digit.
Not used. Must be set to “00”.
✱
22 KEYPAD PANIC
ENABLES (PARTITION
SPECIFIC)
N
0 = disable
1 = enable
Must be set to “000” for partition 1
in fire systems.
✱
23 MULTIPLE ALARMS
(PARTITION SPECIFIC)
N
0 = disable
1 = enable
Must be set to “1” (enabled).
✱
26 INTELLIGENT TEST
REPORTING
N
0 = disable
1 = enable
Must be set to “0” (disable).
✱
27 TEST REPORT INTERVAL
Y
Enter 0001-9999 for the test report
interval in hours.
Enter 0000 for test reporting.
Must be set to “0024” (Maximum 24
hours)
✱
28 POWERUP IN PREVIOUS
STATE
Y
0 = disable
1 = enable
Must be set to “1” (enable).
✱
37 DOWNLOAD COMMAND
ENABLES
N
0 = disable
1 = enable
Must be set to “0” for all entries
(disable).
✱
41 NORMALLY CLOSED OR
EOLR (ZONES 3-8)
N
0 = EOLR supervision
1 = N.C. loops
Must be set to “0” (EOLR
Supervision).
✱
42 DIAL TONE PAUSE
Y
Enter the wait time for dial tone
detection:
0 = 5 seconds; 1 = 11 seconds; 2 = 30
seconds.
Must be set to “0” (5 seconds).
✱
44 RING DETECTION
COUNT
N
Enter 00 to disable ring detection.
Enter 01-14 for ring counts of 1-14.
Enter 15 to select Answering Machine
Defeat Mode
Must be set to “00” (disable).
✱
56 DYNAMIC SIGNALING
DELAY
Y
Enter 00-15 times 15 seconds.
Must be set to “6” (90 seconds).
✱
64
-
✱
76
(
PAGER OPTIONS)
N NA
Not
Used
✱
77 AUTO RESTORE
Y
0 = disable
1 = restore troubles only
2 = restore troubles and fire alarms
Must be set to “1” (restore troubles