– 24 –
Restore/Supervisory Codes
PROMPT
EXPLANATION
RESTR, SUPV. CODE
1 = YES 0 = NO 0
Press
[1]
(Y) to enter Restore and Supervisory Codes for zones.
ENTER ZN FOR GRP
000 = QUIT 001
Enter one zone for each group of 16 zones (001-016, 017-032, etc.).
ALARM RESTORE
GRP 001-016
00
Enter the first digit of the Alarm Restore Report Code for this group of zones (double-digit entry). The
second digit (for two-digit reporting formats) is automatically the ID (second) digit of the Alarm Report Code
for each zone (if programmed).
Press [
✱
] to continue.
TROUBLE
GRP 001-016
00
Enter the first digit of the Trouble Report Code for this group of zones (double-digit entry). The second digit
(for two-digit reporting formats) is automatically the ID (second) digit of the Alarm Report Code for each zone
(if programmed).
Press [
✱
] to continue.
TROUBLE RESTORE
GRP 001-016
00
Enter the first digit of the trouble restore code (single-digit entry) and press [
✱
]. The second digit (for two-
digit reporting formats) is automatically the ID (second) digit of the alarm report code for each zone (if
programmed).
Press [
✱
] to continue.
BYPASS
GRP 001-016
00
Enter the first digit of the Bypass Report Code (double-digit entry) and press [
✱
]. The second digit (for two-
digit reporting formats) is automatically the ID (second) digit of the Alarm Report Code for each zone (if
programmed).
Press [
✱
] to continue.
BYPASS RESTORE
GRP 001-016
00
Enter the first digit of the Bypass Restore Report Code (double-digit entry) and press [
✱
]. The second digit
(for two-digit reporting formats) is automatically the ID (second) digit of the Alarm Report Code for each zone
(if programmed).
Press [
✱
] to continue.
ENTER ZN FOR GRP
000 = QUIT
017
Enter one zone for each group of 16 zones. When you are finished entering Restore and Supervisory Codes
for all zone groups, enter
000
.
Press [
✱
] to continue.
QUIT REPORT MENU
1 = YES 0 = NO
0
If you have completely finished entering report codes, press
[1]
(Y) to quit
Report Code Programming. If
you wish to enter other system report codes, enter
0
(N).
Press [
✱
] to continue.
System Group #1 Codes
PROMPT
EXPLANATION
SYSTEM GROUP #1?
1 = YES 0 = NO 0
To enter System Group #1 codes, press
1
(Y).
CLOSE
1st 00 2nd 00
Enter the first digit of the Closing (Arm-AWAY) report. Press [
✱
]. Enter the second digit of the report. If the
user number is desired as the second digit, enter
01
(not necessary for Contact ID or High Speed formats).
Press [
✱
] to continue.
Summary of Contents for Ademco VISTA-32FB