– 13 –
3*57
BELL 2 & AUX RELAY CONFIRM
[0,0]
ARMING DING
Bell 2 Aux
0=disable; 1=enable.
NOTE: If using a keyfob, when the button is pressed, either
for arming or disarming, the bell will ding indicating that the
button is working.
Must be “1” for Commercial Burglary installations.
3*59
ENABLE BELL 2 & AUX RELAY
[0,0]
CHIME ANNUNCIATION
Bell 2 Aux
0=disable;
1=enable
NOTE:
Must be “0, 0” if Bell 2 or Aux. Relay is used for fire
application.
3*60
BELL 2 & AUX RELAY TIMEOUT
| |
Bell 2 Aux
Enter 00-15 times 2 minutes; 00=no timeout [00,00]
Minimum 16 minutes for Commercial Burglary installations.
3*61
AUX RELAY FUNCTION
[1]
0=trouble/supervisory; 1=alarm, silenced by code = off;
2=smoke detector reset; 3=battery save; 4=alarm, silenced
by code = # = 67
NOTE: See Data Field Descriptions in the Installation and
Setup Guide for specific information.
3*82
ENABLE BURG FEATURES ON PART 1
[1]
0=disable (disables AWAY, STAY, MAX, TEST, INSTANT
and CHIME); 1=enable;
NOTE: Must be "0" for Commercial Fire installations.
3*85
ENABLE FIRE & SYSTEM ZONE BYPASS [1]
0=disable; 1=only installer can bypass;
2=only installer and master can bypass.
Applies to fire zone types 9, 16, 17, and 18 and system
zones 970-977 and to partition 1 only.