4.8 Control Wiring
•
Isolate control wiring from high power components in the adjustable frequency
drive.
•
When the adjustable frequency drive is connected to a thermistor, ensure that
the thermistor control wiring is shielded and reinforced/double insulated. A 24
V DC supply voltage is recommended.
4.8.1 Control Terminal Types
Figure 4.13 and Figure 4.14 show the removable adjustable frequency drive con-
nectors. Terminal functions and default settings are summarized in Table 4.2.
Figure 4.13.
Control Terminal Locations.
Figure 4.14.
Terminal Numbers.
•
Connector 1
provides four programmable digital inputs terminals, two
additional digital terminals programmable as either input or output, a 24 V DC
terminal supply voltage, and a common for optional customer supplied 24 V DC
voltage.
•
Connector 2
terminals (+) 68 and (-) 69 are for an RS-485 serial communication
connection.
•
Connector 3
provides two analog inputs, one analog output, 10 V DC supply
voltage, and commons for the inputs and output.
•
Connector 4
is a USB port available for use with the MCT 10 Set-up Software.
2
3
4
1
130BB921.11
12 13 18 19 27 29 32 33 20 37
39 42 50 53 54 55
61 68 69
130BB931.10
1
2
3
Summary of Contents for 3G SmartVFD HVFD3D2A0020
Page 1: ...3G SmartVFD Installation and User Guide ...
Page 5: ...iv 31 00559 01 ...
Page 15: ...10 31 00559 01 ...
Page 19: ...14 31 00559 01 ...
Page 23: ...18 31 00559 01 ...
Page 53: ...48 31 00559 01 ...
Page 83: ...78 31 00559 01 ...
Page 109: ...103 31 00559 01 ...
Page 125: ...119 31 00559 01 ...
Page 126: ......
Page 127: ... Honeywell 715 Peachtree Street NE Atlanta GA 30308 buildings honeywell com 31 00559 01 08 22 ...