Motor is not
reaching
maximum
speed
Frequency limits set
wrong
Check output limits in 4-
13 Motor Speed High
Limit [RPM], 4-14 Motor
Speed High Limit [Hz]
and 4-19 Max Output
Frequency.
Program correct settings.
Reference input signal
not scaled correctly
Check reference input
signal scaling in 6-0*
Analog I/O Mode and
parameter group 3-1*
References. Reference
limits in parameter group
3-0* Reference Limits.
Check settings in
parameter group 1-6*
Load Depen.Setting. For
closed-loop operation,
check settings in
parameter group 20-0*
Feedback.
Motor runs
rough
Possible
overmagnetization
Check for incorrect motor
settings in all motor
parameters.
Check motor settings in
parameter groups
1-2* Motor Data, 1-3*
Addl. Motor Data, and
1-5* Load Indep. Setting.
Motor will not
brake
Possible incorrect
settings in the brake
parameters. Possible too
short ramp-down times
Check brake parameters.
Check ramp time
settings.
Check parameter group
2-0* DC Brake and 3-0*
Reference Limits.
Open power
fuses or
circuit
breaker trip
Phase-to-phase short
Motor or panel has a
short phase-to-phase.
Check motor and panel
phase for shorts.
Eliminate any short
circuits detected.
Motor overload
Motor is overloaded for
the application.
Perform start-up test and
verify motor current is
within specifications. If
motor current is
exceeding nameplate full
load current, motor may
run only with reduced
load. Review the
specifications for the
application.
Loose connections
Perform pre-start-up
check for loose
connections
Tighten loose
connections.
Line power
current
imbalance
greater than
3%
Problem with line power
(See Alarm 4 Mains phase
loss description)
Rotate input power leads
into the adjustable
frequency drive one
position: A to B, B to C, C
to A.
If imbalanced leg follows
the wire, it is a power
problem. Check line
power supply.
Problem with the
adjustable frequency
drive
Rotate input power leads
into the adjustable
frequency drive one
position: A to B, B to C, C
to A.
If imbalance leg stays on
same input terminal, it is
a problem with the unit.
Contact the supplier.
Symptom
Possible cause
Test
Solution
Summary of Contents for 3G SmartVFD HVFD3D2A0020
Page 1: ...3G SmartVFD Installation and User Guide ...
Page 5: ...iv 31 00559 01 ...
Page 15: ...10 31 00559 01 ...
Page 19: ...14 31 00559 01 ...
Page 23: ...18 31 00559 01 ...
Page 53: ...48 31 00559 01 ...
Page 83: ...78 31 00559 01 ...
Page 109: ...103 31 00559 01 ...
Page 125: ...119 31 00559 01 ...
Page 126: ......
Page 127: ... Honeywell 715 Peachtree Street NE Atlanta GA 30308 buildings honeywell com 31 00559 01 08 22 ...