4.8.4 Voltage/Current Input Selection (Switches)
The analog input terminals 53 and 54 allow setting of input signal to voltage (0–
10 V) or current (0/4–20 mA).
Default parameter settings:
•
Terminal 53: speed reference signal in open-loop (see 16-61 Terminal 53 Switch
Setting).
•
Terminal 54: feedback signal in closed-loop (see 16-63 Terminal 54 Switch
Setting).
Note:
Disconnect power to the adjustable frequency drive before changing switch
positions.
Step 1.
Remove the local control panel (see Figure 4.16.)
Step 2.
Remove any optional equipment covering the switches.
Step 3.
Set switches A53 and A54 to select the signal type. U selects voltage, I
selects current.
Figure 4.16.
Location of Terminals 53 and 54 Switches.
4.8.5 RS-485 Serial Communication
Up to 32 nodes can be connected as a bus, or via drop cables from a common trunk
line to one network segment. Repeaters can divide network segments. Each
repeater functions as a node within the segment in which it is installed. Each node
connected within a given network must have a unique node address across all seg-
ments.
•
Connect RS-485 serial communication wiring to terminals (+) 68 and (-) 69.
130BD530.10
1
2
N O
BUSTER.
OFF-ON
A53 A54
U- I U- I
Summary of Contents for 3G SmartVFD HVFD3D2A0020
Page 1: ...3G SmartVFD Installation and User Guide ...
Page 5: ...iv 31 00559 01 ...
Page 15: ...10 31 00559 01 ...
Page 19: ...14 31 00559 01 ...
Page 23: ...18 31 00559 01 ...
Page 53: ...48 31 00559 01 ...
Page 83: ...78 31 00559 01 ...
Page 109: ...103 31 00559 01 ...
Page 125: ...119 31 00559 01 ...
Page 126: ......
Page 127: ... Honeywell 715 Peachtree Street NE Atlanta GA 30308 buildings honeywell com 31 00559 01 08 22 ...