31-00559-01
61
Trip lock
Input power is cycled. The motor coasts to a stop. The adjustable frequency drive
continues to monitor the adjustable frequency drive status. Remove input power to
the adjustable frequency drive, correct the cause of the fault, and reset the adjust-
able frequency drive.
Warning and Alarm Displays
•
A warning is displayed in the LCP along with the warning number.
•
An alarm flashes along with the alarm number.
Figure 7.2.
Alarm Display Example.
In addition to the text and alarm code in the LCP, there are three status indicator
lights.
Figure 7.3.
Status Indicator Lights. .
7.4 List of Warnings and Alarms
The warning/alarm information below defines each warning/alarm condition, pro-
vides the probable cause for the condition, and details a remedy or troubleshooting
procedure.
WARNING 1, 10 Volts low
The control card voltage is below 10 V from terminal 50. Remove some of the load
from terminal 50, as the 10 V supply is overloaded. Max. 15 mA or minimum 590
Ω
.
A short circuit in a connected potentiometer or improper wiring of the potentiome-
ter can cause this condition.
Warning LED
Alarm LED
Warning
On
Off
Alarm
Off
On (Flashing)
Trip Lock
On
On (Flashing)
130BP086.11
Status
0.0Hz 0.000kW 0.00A
0.0Hz
0
Earth Fault [A14]
Auto Remote Trip
1(1)
130BP086.11
Status
0.0Hz 0.000kW 0.00A
0.0Hz
0
Earth Fault [A14]
Auto Remote Trip
1(1)
Summary of Contents for 3G SmartVFD HVFD3D2A0020
Page 1: ...3G SmartVFD Installation and User Guide ...
Page 5: ...iv 31 00559 01 ...
Page 15: ...10 31 00559 01 ...
Page 19: ...14 31 00559 01 ...
Page 23: ...18 31 00559 01 ...
Page 53: ...48 31 00559 01 ...
Page 83: ...78 31 00559 01 ...
Page 109: ...103 31 00559 01 ...
Page 125: ...119 31 00559 01 ...
Page 126: ......
Page 127: ... Honeywell 715 Peachtree Street NE Atlanta GA 30308 buildings honeywell com 31 00559 01 08 22 ...