(18)
Open the protective relay tray and place the test bank switch
(34, Fig. 2)
in TEST BANK
position.
(19)
Again place the load contactor switch
(20)
in the top, CLOSE position. Light
(22)
should glow
GREEN and remain ON when the switch is released and allowed to return to the center ON
position. This indicates that the test bank switch
(34)
is functioning to by-pass the plug interlock
relay.
(20)
Return the test bank switch to AIRCRAFT position. The load contactor should open at once and
the green indicating light
(22)
should go off.
(21)
Connect a source of 24-V DC power
(two twelve-volt batteries connected in
series) to terminals
“N” and “F”
(or “E”)
at the output terminal panel. Connection polarity should be: MINUS to
terminal N and PLUS to terminal E or F.
(22)
With test-bank switch in AIRCRAFT position, hold the contactor operating switch
(20)
in top,
CLOSE position momentarily. The generator “on” indicating light
(22)
should glow GREEN and
remain on when the switch is released and allowed to return to the center ON position. This
indicates that the load contactor is closed and the plug interlock relay is functioning properly.
(23)
Apply 1/3 to 1/2 load at the load bank and allow the unit to run for 15 to 30 minutes. Observe
operation of all monitoring instruments.
(24)
Increase load bank resistance to apply a full load.
(25)
Check operation of the governor by observing the frequency meter
(1, Fig. 2)
when generator is
switched from no-load to full-load and vice versa. Use the contactor control switch
(20)
to apply
and remove load several times. Frequency drop should be no more than 1 Hz. Adjust governor
if necessary
(see Para. 4, E, (3)).
(26)
Follow instructions in Para. 4, B,
(2) (b)
to set voltage regulator linedrop compensation
potentiometers
(Ref. Figure 2, items (38) and (39)).
Set knob pointer on cable size
potentiometer
(39)
to size
(2/0, 4/0, etc.)
of cable being used. Set knob pointer on cable length
potentiometer
(38)
to length
(20 feet, 40 feet, etc.)
of cable being used. See instruction plate
(mounted below knobs).
(27)
Check voltage regulator, at intervals, from no-load to full load, and on up to 125% load. Observe
and note voltage at various loads. Voltages should vary no more than plus or minus 1% from
115 V.
(28)
Check accuracy of voltmeter.
a. Open generator control tray (14, Fig. 2).
b. Connect a master voltmeter of known accuracy to terminals of the voltmeter (2).
c. Compare unit voltmeter reading with master meter. Error must not exceed 2% of full scale.
(29)
Check accuracy of AC ammeter.
a. Connect a master ammeter of known accuracy to the AC ammeter (4) terminals.
b. Compare unit ammeter reading with master meter under various loads. Error must not
exceed 4% of full scale.
(30)
Check operation of meter selector switch
(5).
A voltage value should be shown in each switch
position.
(31)
Check operation of the line switch
(6).
A normal voltage of 115 V AC should be indicated when
the switch is in LINE-TO-NEUTRAL position. A voltage of approximately 200 V AC should be
indicated when the switch is placed in LINE-TO-LINE position.
(32)
Check accuracy of frequency meter.
OM-499
May 31/94 Revised
2-3
Page 7
Summary of Contents for 6824-1
Page 2: ...This page intentionally left blank...
Page 6: ...This page intentionally left blank OM 499 Safety Warnings May 31 94 Revised Page 4...
Page 8: ...This page intentionally left blank OM 499 Introduction May 31 94 Revised Page 2...
Page 14: ...This page intentionally left blank OM 499 Table of Contents May 31 94 Revised Page 6...
Page 40: ...This page intentionally left blank OM 499 1 1 May 31 94 Revised Page 26...
Page 66: ...Engine Control Panel in Tilt out Position Figure 8 OM 499 2 1 May 31 94 Revised Page 12...
Page 90: ...No 2 Output on Dual Output Units Figure 13 OM 499 2 3 May 31 94 Revised Page 20...
Page 98: ...This page intentionally left blank OM 499 3 1 May 31 94 Revised Page 8...
Page 114: ...This page intentionally left blank OM 499 3 1 May 31 94 Revised Page 24...
Page 122: ...Generator Set Figure 1 OM 499 4 3 May 31 94 Revised Page 2...
Page 124: ...Canopy Assembly Figure 2 OM 499 4 3 May 31 94 Revised Page 4...
Page 126: ...This page intentionally left blank OM 499 4 3 May 31 94 Revised Page 6...
Page 128: ...Canopy Assembly Figure 3 OM 499 4 3 May 31 94 Revised Page 8...
Page 130: ...This page intentionally left blank OM 499 4 3 May 31 94 Revised Page 10...
Page 132: ...Generator Set Without Canopy Figure 4 OM 499 4 3 May 31 94 Revised Page 12...
Page 134: ...This page intentionally left blank OM 499 4 3 May 31 94 Revised Page 14...
Page 136: ...Radiator and Cooling System Group Figure 5 OM 499 4 3 May 31 94 Revised Page 16...
Page 138: ...Air Cleaner Assembly Figure 6 OM 499 4 3 May 31 94 Revised Page 18...
Page 142: ...Fuel Lines Assembly Figure 8 OM 499 4 3 May 31 94 Revised Page 22...
Page 144: ...Oil Line Assembly Figure 9 OM 499 4 3 May 31 94 Revised Page 24...
Page 146: ...Fuel Oil Lines Figure 10 OM 499 4 3 May 31 94 Revised Page 26...
Page 148: ...Fuel Oil Lines Figure 11 OM 499 4 3 May 31 94 Revised Page 28...
Page 150: ...Stator Terminal Panel Assembly Figure 12 OM 499 4 3 May 31 94 Revised Page 30...
Page 152: ...Power Module Panel Assembly Figure 13 OM 499 4 3 May 31 94 Revised Page 32...
Page 154: ...This page intentionally left blank OM 499 4 3 May 31 94 Revised Page 34...
Page 156: ...Control Box Assembly Figure 14 OM 499 4 3 May 31 94 Revised Page 36...
Page 158: ...Generator Controls Tray Assembly Figure 15 OM 499 4 3 May 31 94 Revised Page 38...
Page 160: ...This page intentionally left blank OM 499 4 3 May 31 94 Revised Page 40...
Page 162: ...Protective Relays Tray Assembly Figure 16 OM 499 4 3 May 31 94 Revised Page 42...
Page 164: ...This page intentionally left blank OM 499 4 3 May 31 94 Revised Page 44...
Page 166: ...Control Box and Internal Components Group Figure 17 OM 499 4 3 May 31 94 Revised Page 46...
Page 168: ...Engine Control Panel Assembly Figure 18 OM 499 4 3 May 31 94 Revised Page 48...
Page 170: ...This page intentionally left blank OM 499 4 3 May 31 94 Revised Page 50...
Page 172: ...Output Terminal Board Assembly Figure 19 OM 499 4 3 May 31 94 Revised Page 52...
Page 174: ...Generator Group Figure 20 OM 499 4 3 May 31 94 Revised Page 54...
Page 176: ...Mounting Frame and Lifting Yoke Assembly Figure 21 OM 499 4 3 May 31 94 Revised Page 56...
Page 178: ...Auxiliary Frame and Components Group Figure 22 OM 499 4 3 May 31 94 Revised Page 58...
Page 180: ...Electric Governor Assembly OM 499 4 3 May 31 94 Revised Page 60...
Page 182: ...This page intentionally left blank 4 3 March 31 74 Revised Page 21A OM 499...
Page 194: ...This page intentionally left blank OM 499 4 4 May 31 94 Revised Page 12...
Page 196: ...This page intentionally left blank OM 499 5 0 May 31 94 Revised Page 2...
Page 198: ...This page intentionally left blank OM 499 6 0 May 31 94 Revised Page 2...
Page 199: ......
Page 200: ......
Page 201: ......
Page 202: ......
Page 203: ......
Page 204: ......
Page 205: ......
Page 206: ......
Page 207: ......
Page 208: ......
Page 209: ......
Page 210: ......
Page 212: ...This page intentionally left blank OM 499 Unusual Service Conditions May 31 94 Revised Page 2...
Page 214: ......