
ENGLISH
In case of test run, user can also select the mode of the test (cooling or heating).
When user confirms the test run or the air purge, the YUTAKI user controller sends the order to the indoor.
During the execution of this test, the following screen is shown:
•
When the test starts, the user controller will exit from the installer mode.
•
User can cancel the test run regardless of the time left for test finishing.
•
The Test Run icon is shown in the notifications zone, but the notification of this test run is taken from H-LINK.
When test run has finished, an information message is displayed in the screen, and pressing accept, the user returns to the global
view.
?
N O T E
• When commissioning and installing the unit, it is very important to use the “Air purge” function to remove all the air in the water circuit. When the air
purge function is running, the water pump starts the automatic air venting routine which consists of regulating the speed and open/close configured
3-way valve to help to evacuate air from the system.
• For Outdoor test run, refer to Outdoor Unit Installation Manual.
• If there is a Heater or a Boiler installed, disable the operation before running the test run.
COMMISSIONING
PMML0575 rev.2 - 03/2022
347