Example 4
1
PC-ARFH1E attached into the unit and used as unit controller and room thermostat for both zones.
2
Wired room sensor for Zone 1
3
Wired room sensor for Zone 2
Outdoor unit
OK
Indoor unit
1
Living room Zone 1
Bedroom Zone 2
Order
FIRST
Type
Master
Unit + Circuits
Questions
Answers
Is this device attached to the unit?
YES
Is this device used as a Room Thermostat of a zone?
YES, IN BOTH ZONES
Which are the emitters of circuit 1?
Underfloor heating
Which are the emitters of circuit 2?
Underfloor heating
Do you have domestic hot water tank?
NO
Do you have swimming pool?
NO
Do you have boiler?
NO
Do you have electric backup heater?
NO
COMPLETED
?
N O T E
•
After finishing Configuration assistant, go to Input&Outputs&Sensor menu and select which auxiliary sensor do you want to use for ambient
temperature in each zone.
• Example:
REF
Access
Description
Default Value
Selected value
Auxiliary Sensors
Taux1
Sensor 1 (Taux1)
Two3 (if Boiler)
C1 Ambient
Taux2
Sensor 2 (Taux2)
Swimming pool (if SWP existing)
C2 Ambient
Taux3
Sensor 3 (Taux3)
Outdoor Sensor
-
UNIT CONTROLLER (PC-ARFH1E)
PMML0575 rev.2 - 03/2022