4.4 Transmission wiring between RASC and indoor unit
• The transmission is wired to terminals 1-2.
• The H-LINK II wiring system requires only two transmission cables that connect the indoor unit and the RASC unit.
1
1
2
2
Indoor unit
Outdoor unit
• Use twist pair wires (0.75 mm²) for operation wiring between RASC unit and indoor unit.
• The wiring must consist of 2-core wires (Do not use wire with more than 3 cores).
•
Use shielded wires for intermediate wiring to protect the units from noise interference, with a length of less than 300m
and a size in compliance with local codes.
•
In the event that a conduit tube for field-wiring is not used, fix rubber bushes to the panel with adhesive.
!
C A U T I O N
Ensure that the transmission wiring is not wrongly connected to any live part that could be damaged the PCB.
4 Electrical and control settings
Transmission wiring between RASC and indoor unit
SMGB0091 rev.2 - 11/2015
63