10 Troubleshooting
Troubleshooting procedure
SMGB0091 rev.2 - 11/2015
231
10
Alarm code
35
Incorrect Indoor number setting
This alarm code appears under any of the following conditions:
• Wrong indoor unit address (DSW6 + RSW1)
• Duplicated RASC unit refrigerant system setting or wrong refrigerant system DSW settings (DSW4 + RSW1).
• When the indoor and RASC unit refrigerant system and address are set to 64 or above. (In such a case, the alarm
code “b1” appears on the remote control switch).
• Error in the number of connected indoor units not compatible with H-LINK II. (In this case, the alarm code “b5” is
flashing on the RASC unit PCB1).
-
Number of connected indoor units compatible with H-LINK II in the same refrigerant group exceeds 16 units.
-
In systems with indoor units compatible and not compatible with H-LINK II if there is no empty space in addresses
0~15 because these numbers have already been fixed for indoor units compatible with H-LINK II.
?
N O T E
The alarm code may appear when H-LINK system is employed for indoor-RASC unit transmission, if there is any incorrect setting in
DSW4/RSW1 on the RASC unit PCB and DSW5/RSW2 on the indoor unit PCB; which are dip switches used for refrigerant system setting.
In such a case, turn OFF the power and correctly set DSW4/RSW1 on the RASC unit PCB and DSW5/RSW2 on the indoor unit PCB
before reactivating the power.
(Some indoor unit models do not have RSW2.)
Alarm code
36
Incorrect indoor unit combination
This alarm code is indicated when the indoor unit connected to the RASC unit is for other refrigerants (R22 or R407C).