10 Troubleshooting
Troubleshooting procedure
SMGB0091 rev.2 - 11/2015
211
10
RASC-(8/10)HNPE
Is LED2 (Green) on PCB1
flashing?
Does LED2 (Green)
flashing speed become faster
than before?
Is LED201 on PCB4 ON?
Is LED201 on PCB4 ON?
Faulty PCB4
Broken wiring or insufficient
contact of the wiring between
PCB1 and PCB4
Faulty PCB4
Faulty PCB1
Broken wiring or insufficient
contact of the wiring between
PCB1 and PCB4
Yes
Yes
Yes
Yes
No
No
No
No
Check the wiring and repair it
(Broken or wrong wiring)
Repair fuse if blown
No
No
Yes
Yes
Check the wiring again. PCB1 and PCB4 are
normal (*2)
Disconnect CN6 of PCB1 and
then power ON.
No
Yes
Reconnect CN6 on PCB1
Faulty (Loose wiring,
change of colour)
Normal
Faulty PCB1.
Replace capacitors (CB1, CB2) and/or resistances
(R1,R2) (*2)
?
N O T E
Investigate the cause of fuse blown.
Are the fuse (EF1)
on PCB1 and power fuses
(EF1,EF2) normal?
Is LED2 (Green) on PCB1
flashing?
Check capacitors (CB1,
CB2) and resistances (R1,R2)
(*1)
Is wiring between CN6 on
the PCB1 and CN206 on the
PCB4 correctly connected?
PCB1: Control PCB in outdoor unit
PCB4: Inverter PCB in outdoor unit
?
N O T E
• *1): For checking the capacitors, please refer to the sections
“Checking capacitors CB1 and CB2”
and
• *2): Regarding replacing or checking method for the inverter PCB and its components, refer to the paragraph
in
section